
Implementation of Modbus TCP
D301271 1013 - FGEN - multi protocol
9-18
9.3.7
Register 0×113E und 0×113F: „Save Modbus-Connection-Parameters“
Registers 0×113E and 0×113F are used for the non-volatile saving of parameters in registers 0×1120
and 0×1130 to 0×113B.
or this purpose, write "0×7361" in register 0×113E. To activate the saving of the registers, write
"0×7665" ("save") within 30 seconds in register 0×113F.
Both registers can also be written with one single request using the function codes FC16 and FC23.
Содержание FGEN-AIM Series
Страница 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Страница 8: ...D301271 1013 FGEN multi protocol vi...
Страница 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Страница 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Страница 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Страница 104: ...Application example FGEN for EtherNet IP with Allen Bradley PLC and RS Logix 5000 D301271 1013 FGEN multi protocol 8 14...
Страница 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Страница 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...