Application example FGEN for Modbus TCP with CODESYS Win V3
D301271 1013 - FGEN - multi protocol
10-22
4
Write:
Parameters
of the station FGEN-XSG16-5001
target
→
inverting the input signal at channel 5
Writing parameters is normally done once during the program start and is thus not set as a "normal"
Modbus channel under "ModbusSlave Channel", but as an Initialization channel under "
Modbus
Slave Init
Setting the initialization channel for the parameterization
).
–
Access Type:
Write Single Register (function code
06
)
–
Write Register, Offset:
0×B001
Register mapping of the FGEN-stations
The parameters of the station can be found in register 0xB000 to 0×B003.
Parameterization of the station
The parameterization to be done here is to invert the input signal at channel 5 (I.5) of the station
(register 0×B001, bit 5).
The parameter register is build up as follows:
A 2
5
=
32
will be written to register
0×B001
, which results from the station's the parameter byte
assignment.
Reg.
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0×B000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0×B001
Inv. DI7
Inv. DI6
Inv. DI5
Inv. DI4
Inv. DI3
Inv. DI2
Inv. DI1
Inv. DI0
Inv. DI15
Inv. DI14
Inv. DI13
Inv. DI12
Inv. DI11
Inv. DI10
Inv. DI9
Inv. DI8
0×B002
SRO7
SRO6
SRO5
SRO4
SRO3
SRO2
SRO1
SRO0
SRO15
SRO14
SRO13
SRO12
SRO11
SRO10
SRO9
SRO8
0×B003
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Figure 10-21:
Setting the ini-
tialization chan-
nel for the
parameteriza-
tion
Содержание FGEN-AIM Series
Страница 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Страница 8: ...D301271 1013 FGEN multi protocol vi...
Страница 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Страница 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Страница 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Страница 104: ...Application example FGEN for EtherNet IP with Allen Bradley PLC and RS Logix 5000 D301271 1013 FGEN multi protocol 8 14...
Страница 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Страница 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...