Implementation of Modbus TCP
D301271 1013 - FGEN - multi protocol
9-16
9.3.3
Register 100Ch: "Station status"
This register contains a general gateway/ station status.
Table 9-7:
Register 100Ch:
Station status
Bit
Name
Description
Station
15
-
-
14
FCE
The Force Mode is activated, which means, the actual
output values may no match the ones defined and sent by
the field bus.
13
-
-
12
-
-
Module bus
11
CFG
I/O configuration error
10
COM
Communication on the internal module bus disturbed.
Voltage errors
9
U
B
System supply voltage too low (< 18 V DC).
8
-
-
7
U
L
Load voltage too low (< 18 V DC).
6
-
-
5
-
-
4 -
-
Warnings
3
-
-
2
-
-
1
-
-
0
DiagWarn
Diagnostic messages are available.
Содержание FGEN-AIM Series
Страница 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Страница 8: ...D301271 1013 FGEN multi protocol vi...
Страница 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Страница 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Страница 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Страница 104: ...Application example FGEN for EtherNet IP with Allen Bradley PLC and RS Logix 5000 D301271 1013 FGEN multi protocol 8 14...
Страница 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Страница 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...