FGEN – general technical properties
D301271 1013 - FGEN - multi protocol
3-8
3.5
Address assignment
Setting the address mode is done through the 3 rotary coding-switches on the gateway.
3.5.1
Default setting of the gateway
The stations' default-settings are as follows:
IP-address
192.168.1.254
subnet mask
255.255.255.0
default gateway
192.168.1.1
3.5.2
Resetting the IP-address, switch position "000"
By setting the rotary coding switches to "000" followed by a voltage reset, the module is set to the
address 192.168.1.254 for IP-based services (see
Default setting of the gateway (page 3-8)
).
The I/O-ASSISTANT can, for example, communicate with the station in this switch position.
Figure 3-6:
Decimal rotary
coding-switches
for address
setting
Attention
The cover of the decimal rotary coding-switches must be closed by tightening the screw after
use.
The seal in the cover must not be damaged or slipped.
The protection class IP67 can only be guaranteed when the cover is closed correctly.
Note
After every change of the address-mode, a reset must be carried out.
Note
The stations can be reset by the user to these default settings at any time.
To reset the module, set the three coding-switches on the gateway to "000" followed by a
power-on reset.
Note
Setting "000" is no operation mode! Please set the device to another mode after having
reset the IP address to the default values.
x 10
x 1
1
2
3
4
5
6
7
8
9 0
1
2
3
4
5
6
7
8
9 0
1
2
3
4
5
6
7
8
9 0
000: 192.168.1.254
1 - 254: static rotary
300: BootP
400: DHCP
500: PGM
600: PGM-DHCP
900: F_Reset
x 100
Содержание FGEN-AIM Series
Страница 1: ...USER MANUAL FGEN AIM stations with multi FUNTIONALITY Sense it Connect it Bus it Solve it...
Страница 8: ...D301271 1013 FGEN multi protocol vi...
Страница 14: ...About this manual D301271 1013 FGEN multi protocol 1 6...
Страница 42: ...Digital inputs FGEN IM16 x001 D301271 1013 FGEN multi protocol 4 4...
Страница 46: ...Digital outputs FGEN OM16 x001 D301271 1013 FGEN multi protocol 5 4...
Страница 104: ...Application example FGEN for EtherNet IP with Allen Bradley PLC and RS Logix 5000 D301271 1013 FGEN multi protocol 8 14...
Страница 126: ...Implementation of Modbus TCP D301271 1013 FGEN multi protocol 9 22...
Страница 186: ...Guidelines for Electrical Installation D301271 1013 FGEN multi protocol 13 8...