D301271 1013 - FGEN - multi protocol
10-7
Programming with CODESYS
10.3.3
Defining the communication settings
Double-clicking the "Device (CODESYS Control Win V3)" opens the corresponding editors.
The communication path (Gateway) to the HMI is defined in the "Communication Settings" tab.
Gateway definition
1
Use the "Add gateway"-button to open the dialog box "Gateway" and, where necessary, assign a
new gateway name.
2
Keep the setting "localhost" or define an IP-address for the gateway instead.
When using the setting "localhost“, the CODESYS-communication-gateway of the PC, on which this
CODESYS-installation is running, is used as programming interface.
Figure 10-6:
Communica-
tion settings