31
TTL air curtain systems - Controller TWICS
10. Connecting device - start up (cont.)
10.2 Connecting control panel
Inside the controller are available one CAN bus connection socket
for the data line to air curtain unit and sereral clambs for
connecting an analoque sensor and an outside sensor to display
temperatures at the screen (alternative to connection
at the internal connecting board (PCB)).
X3 1
Analogue sensor
2
Analogue sensor
3
Free
X4 1
Outside sensor
2
Outside sensor
3
Free
Bu1
CAN bus connection (data line) Western-Modular, 6-wire.
10.3 Enable signals
The start of the air curtain system can set depending by an BMS enable signal (see menu 3.4 Basic set-
tings -
DDC enable GLOBAL
). The signal is to applicate to the clambs 16/17 at the internal connecting
board (PCB).
At these BMS enable the MANUAL mode can be involved or excluded by choosing in menu 3.5 (Basic
settings -
DDC enable MAN.MODE
).
10.4 Restart
A restart of the air curtain unit after a general shut-off in cause of a fault is depending on aknowledge-
PHQWVUHVSFDQPDGHGHSHQGLQJRQFRQÀUPLQJV
Power interruption - in case of power interruption and suddenly recurrency of voltage a self-acting
UHVWDUWLVEORFNHG7KHDLUFXUWDLQXQLWLVDWÀUVWWRVKXWRIIE\WKH2))EXWWRQDQGWKHQWRUHDFWLYD
te by choose of operation mode and the performance level or operating stage.
Motor fault - in case of motor fault (triggering of thermo contacts) the fault is to quit by shut-off the
air curtain unit with the OFF(0) button and to restart renewed. The motor fault will be collect statisti-
cally and is accessible by menu 2.1 (
6WDWLVWLFV
).
In case of recurring motor faults pleas contact the TTL service immidiately.
Shut-up after frost alert (only with a implemented frost alert thermostat) - a restart after frost alert
FDQPDGHGHSHQGLQJRIDFRQÀUPLQJVHHPHQX%DVLFVHWWLQJV
Aut.start after frost.
).
Note: the shut-up in case of frost alert prevents through the operation interrupt only a further lost of
heat from the already undercooled air curtain system.
Because of the circumstance that a frost alert usually is accompanied by a malfunction of the heating
supply system, the normalizing of temperatures at the heating battery and the restart of the air cur-
tain guaranties not that there is no frost demage entered at the heating battery.
We recommend strongly, after a frost alert case and following normalization of the heating supply to
inspect the unit of possible water leakage!