8. Menu guidance - menu tree (cont.)
3 Basic settings
1
Overrun time
Preselection of overrun time for
AUTOMATIC mode
1-1000 (sec)
180
2
Heating stage
Preselection of operating satge for
HEATING mode at closed door
1-5
1
3
Aut.start after frost
Restart after frost shut down
0=NO / 1=YES
1
4
DDC enable GLOBAL
Activation DDC enable general
0=NO / 1=YES
1
5
DDC enable MAN.MODE. Activation DDC enable for HAND
mode (additional blocking function)
0=NO / 1=YES
0
6
WINTER mode 26-27
Status clambs 26-27
0=NO / 1=YES
0
7
Monitoring PCBs
Default number of internal connection
boards(PCB)/group at groupings
0 =OFF /
1-20=numb. of PCB
0
8
Overrun time prev. vers.
Adaptility for older types of PCB
without importance 180
9
Auto contact delay
Switching delay for Automatic contacts 0-250 (sec)
0
10
Quick start -%
Rot. speed standby, preselection value
10-20 (%)
12
11
Quick start -time
Rot. speed standby, time to setback
0-60 (min)
0
12
RT switches SV
Heating ON/OFF via room thermostat 0=NO / 1=YES
0
13
Auto cont. inverted
Switch over for automatic contact
(changes from NO to NC)
0=NO / 1=YES
0
14
Operation mess. active
Switch over for operation message
„Ready for operation“ or „Operation“
0=NO / 1=YES
1
15
°C active
Display of temperatures at main display
0=NO / 1=YES
0
16
Cold air roller -%
Presetting intension cold air outlet
compared to warm air outlet (forerun-
ning value)
0 .. 200 (%)
100
17
Cold air roller -link
9ROXPHSRZHUDLUÁRZSHUIRUPDQFH
warm air and cold air outlet coupled
0=NO / 1=YES
0
18
7LPHÀOWHUFKDQJH
9DOLGRSWLPHXQWLOQH[WÀOWHUFKDQJLQJ
0=OFF / 1-1000 (h) 288
Main menu point
Nr.
Submenu
Function
Parameter / Default
4 Analogue input
1
VOL via Ext. 0-10 V
External control of volume controller 0=OFF
1=GLOB. / 2=LOC.
0