10. Connecting device - start up
10.1 Internal connecting board (PCB)
The internal connecting board is implemented inside of the air curtain unit. External control contacts like e.g.
DDC enable, door contact etc. will be connected at these internal connecting board.
N
Neutral conductor for power supply (230 V~)
L
Phase power supply (230 V~)
PE
Protective conductor
PE
Protective conductor selenoid valve
N
Neutral conductor solenoid valve (230 V~)
MV
Phase-switched solenoid valve (230 V~)
9
Pot. free operating message (NO)
10
Pot. free operating message (NO)
11
Pot. free fault message (COM)
12
Pot. free fault message (NC)
13
Pot. free fault message (NO)
14
Frost protection thermostat, optional (12 V, internal interconnection)
15
Frost protection thermostat, optional (input, internal interconnection)
16
DDC enable (int. 12 V)
17
DDC enable (input)
18
Automatic contact (int. 12 V)
19
Automatic contact (input)
20
Room thermostat-heating mode within automatic mode (int. 12 V)
21
Room thermostat-heating mode within automatic mode (input)
26
SUMMER/WINTER switchover (int. 12 V)
27
SUMMER/WINTER switchover (input)
42/43
Analogue sensor (for air volume control, anstelle IR-Sensor)-not for ASP 5
52/53
Outside sensor (for Absenkbetrieb)-not for ASP 5
Bu1
&$1ÀHOGEXVFRQQHFWLRQ:(67(510RGXODUFRQQHFWRUSROH
Bu2
&$1ÀHOGEXVFRQQHFWLRQ:(67(510RGXODUFRQQHFWRUSROH
(Connecting sequence Bu1 and Bu2 are interchangeable)
Other clambs internal interconnected or without function!
LED
The LED must blinking.
Otherwise there is a problem with the data line.
Functional switch over GLOBAL/LOCAL at multi unit operation
Jumper inserted = global = all air curtain units
BR1
switches off in case of motor faulty or frost alert
BR2
are in operation, if a automatic contact is connected
BR3
are in operation, if a room thermostat is connected
BR4 Internal
BR5
Internal (only ASP 5 and ECP-X)
BR6
Internal (only ASP 5 and ECP-X)
BR7
Internal (only ECP-X)
BR8
Internal (only ECP-X)
Jumper replaced = local = only the concerning air curtain unit
BR1
with motor faulty or frost alert switchs off, the other units keep in operation
BR2
react to the connected automatic contact
BR3
react to the connected room thermostat
BR4 Internal
BR5
Internal (only ASP 5 and ECP-X)
BR6
Internal (only ASP 5 and ECP-X)
BR7
Internal (only ECP-X)
BR8
Internal (only ECP-X)
Delivery status: BR1 - BR3(BR8) - inserted
If both BUS sockets are occupied, jumper „BR-CAN“ must be replaced!
LED
BR1
BR2
BR3
BR4
BR5
BR6
27
27
25
24
23
22
21
20
19
18
17
16
N L PE PE N MV
9 10
14 15
BR-CAN
11 12 13
Interal connecting board ASP-5
Internal connecting board ECP-S
Bu1
Bu2
N L PE PE N MV
9 10
11 12 13
16 17 18 19
20 21 26 27 GN
D
GN
D
32 33
14
15
BR1
BR2
BR3
BR4
Internal connecting board ECP-X
N L PE PE N MV
Bu1
9 10
Bu2
11 12 13
BR1
BR2
BR3
BR4
BR5
BR6
BR7
BR8
delivery status: bridged
delivery status: bridged
16 17 18 19
20 21 22 23 24 25 26 27 28 29
30 31 32 33
34 35 36 37 38 39 40 41 42 43
14
15
50
51
52
53
30
31
32
33
34
35
36
37
38
39
40
41
42
43
L‘ K1 K2 K3
54
55 56
Bu1
Bu2