TTL air curtain systems - Controller TWICS
6. Operating modes (cont.)
6.5 Energy saving functions
For an especially and energy saving operation of air curtain system(s) ca be activated special functions:
Output performance coupling of both air outlet systems
The air curtain system TWIN
OR
DFKLHYHVLWVKLJKHIÀFLHQF\E\DVSDWLDOO\VHSDUDWLRQRIERWKDLURXWOHWV\VWHPV
implemented in device. The heated interior main- or warm air curtain is upstreamed by a contra-directional
ÁRZLQJRXWHUXSVWUHDPRUFROGDLUFXUWDLQZKLFKJHQHUDWHVDHVVHQWLDOSURSRUWLRQRIVKLHOGSHUIRUPDQFHDQG
SUHYHQWVDGLUHFWWDQJHQF\RIZDUPDLUFXUWDLQZLWKWKHFROGRXWVLGHDLU7:,1WHFFRXQWHUÁRZSULQFLSOH
By a controlled coupling of both air curtain outlets the upstream air curtain outlet can attched a weighting, in
order to intercept simple shield tasks primarily without additional expenditure of heating energy by running
DKHDGLQSHUIRUPDQFHRIWKHFROGDLUFXUWDLQDQGKRRNXSWKHPDLQZDUPDLUFXUWDLQQRWXQWLODWDSUHGHÀQHG
operating value of the upstreamed cold air curtain. This restrict the energy expenditure by heating to the actu-
ally needed operating values.
The operational coupling of warm air and cold air outlet performance can setted in menu 3.17 -
Cold air roller
-link
. In menu 3.16 -
Cold air roller -%
will be determined the intensity of cold air outlet compared to the warm
air outlet performance. Thereby a valutation is possible from 0 % up to 200 %, at that 100% matches the same
performance value as the warm air outlet full duty rated (e.g. both 80% at stepless control, or both step 4 at
stepped control). At an adjustment of 200 % the cold air outlet is running ahead 100% (e.g. cold air outlet 80%
- warm air outlet 40% at stepless control, or cold air outlet step 4 - warm air outlet step 2 at stepped control).