24
O Version & I Version
TSOL series inverter provides two versions for customer to choose based on the local
rules.
“
O Version
”
means inverter needs to install an outer changeover device for EPS
function. This version applies to the wiring rules which allow Neutral line of alternative
supply can be isolated or switched (applies to most of the countries).
“
I Version
”
means inverter has an build-in changeover switch. This version applies to the
wiring rules which require Neutral line of alternative supply must not be isolated or
switched (applies to wiring rules AS/NZS3000:2014 of Australia and New Zealand).
Auto & Manual
EPS function can be achieved automatically or manually according to user
‟s wishes.
For
“
I Version
”
inverter, EPS function can only be triggered automatically.
For
“
O Version
”
inverter, EPS function can be triggered either automatically or manually
according to user
‟s preference.
If user wants to use this function manually, it will need to be installed an external switch.
Please refer to specific wiring diagram below.
For automatic solution, please contact our sales.
PE
EPS breaker