You must allow 1U (44mm or 1.75 inches) of vertical space for each system you install in the rack.
Rack cabients that meet EIA-310D standards have a pattern of three holes per rack unit with
center-to-center holes spacing (beginning at the top holes of a 1U space) of 0.625” ,0.625”, and
0.5inch ( in metric: 15.9mm, 15.9,, and 12.7mm ) for the front and rear vertical rails. Rack cabient
usually have round or square holes.
NOTICE: Some vertical rails may be marked by horizontal lines and numbers in 1U
increments. You can make a note of the number marking on the rack’s vertical rail.
1U (1.75 inch)
0.5 inch
0.5 inch
0.625 inch
0.625 inch
Mark on the narrow area between two holes spacing
Following these steps to mark the rack
1
2
Place a mark on the rack’s front vertical rails where you want to locate the bottom of the
system you are installing in the rack cabient
Place a mark 1.75inch above the original mark you made ( or count up three holes in a
rack that meets EIA-310D standards)
Figure 36 Marking on the rack
4.2.1 Marking the rack
0.5 inch
0.5 inch
0.625 inch
0.625 inch
22
23