TSI Power Corporation MC80023,4,5,6,7,8,9,30
ATS-500 Series Automatic Transfer Switches Rev. 7, September, 2019
TSI Power Corporation Proprietary Information
16
3.4 VOLTAGE SELECTION
3.41 If you have a 208, 220 or 240 V ATS the voltage selection can be changed. The
factory setting is either set to HIGH (220 to 240 V) or LOW (208 V) depending on
what ATS model was ordered. If the factory preset is not desired, performing the
following steps will change the voltage transfer points.
3.42 Make sure both Primary and Backup AC sources to the ATS are de-energized.
3.43 Remove the ATS case cover.
3.44 Locate the jumper at JP1 (HIGH) or JP2 (LOW). See Figures 7 or 8.
3.45 To change the voltage selection simply move the Jumper from the JP1 (HIGH) to
JP2 (LOW) position or JP2 (LOW) to JP1 (HIGH) position (depending on the factory
preset of your ATS).
3.46
Replace ATS case cover.
3.5 INSTALLING THE ATS-500 SERIES
3.51 After the unit has been unpacked and inspected, attach any mounting brackets
that may have optionally been ordered to the ATS using the MC4000C for Wall or
Floor-Mount kits, not shown. If mounting brackets have not been ordered, place
the unit at the desired location near the load. Make sure that the unit has sufficient
surrounding space to provide ample air movement for ventilation.
3.6
CONNECTIONS (HARDWIRE VERSIONS)
NOTES:
1)
Torque terminations for 15, 20 or 30 A units are 0.79 Nm ( 7 in-lb) and for the 40 A
units are 2.26 Nm (20 in-lb).
2)
Be sure to follow electric safety and installation codes in the country of use.
3.61
Make sure that the up-stream Primary and Backup AC sources are de-energized
(switched OFF).
3.62
Incoming Primary and Backup Power Input, as well as, AC Power Output is
through the circular hole in the rear plate of the unit. Remove the rear plate and
save hardware before proceeding.
3.63 For units w/15 A Circuits Breakers use minimum 14 AWG (2.5mm²) wire [preferably
12 AWG (4mm²)]