TSI Power Corporation MC80023,4,5,6,7,8,9,30
ATS-500 Series Automatic Transfer Switches Rev. 7, September, 2019
TSI Power Corporation Proprietary Information
25
6.15
MC80027 ATS-500 SERIES HARDWIRE, 208, 220 and 240 V, Models 500-3800,
-5800, -7800, -9800, -3000, -5000, -7000 AND -9000
SPECIFICATION
ATS-500-
3800
ATS-500-
5800
ATS-500-
7800
ATS-500-
9800
ATS-500-
3000
ATS-500-
5000
ATS-500-
7000
ATS-500-
9000
ELECTRICAL
VA at 208 V
3120
4160
6240
8320
VA at 220 V
3300
4400
6600
8800
VA at 240 V
3600
7200
9600
Current rating
15 A
20 A
30 A
40 A
15 A
20 A
30 A
40 A
Switching technology
Mechanical relays
INPUT
Voltage range: 208 V
166 - 239 V ± 2.5 % nominal
Voltage range: 220 V or 240 V
184 - 264 V ± 2.5 % nominal
Frequency range
47 to 63 Hz, Caution: Both sources must use same nominal frequency
Transfer time
Under one cycle
AC input connections
Hardwire terminals
OUTPUT
Voltage / Current
208 V / 15, 20, 30 or 40 A
220 or 240 V / 15, 20, 30 or 40 A
Load regulation
1 % from no load to full load
Power efficiency
99 % or higher
AC distribution
Hardwire terminals
LED indicators:
Green: Primary output, Yellow: Backup output, Red: Primary or backup AC is out of
tolerance
Audible alarm
Buzzer beeps when loss of primary or backup AC occurs
Audible alarm on / off
Enable / Disable switch
Alarm contacts
Rear-mounted DB-9 connector sends loss of primary / backup AC
PHYSICAL
Dimensions: Inches / mm
W: 11.25" / 286 mm H: 3" / 76 mm D: 11.5" / 292 mm
Weight: lbs / kg
8 lbs / 3.63 kg
Wall or floor mount kit
MK-4000C
ENVIRONMENTAL
Ambient temperature
32° to 104° F (0° to 40° C)
AGENCY APPROVALS
Safety
UL 60950-1 Issue: 2007/03/27 Ed:2 UL Standard for Safety Information Technology
Equipment - Safety - Part 1: General Requirements - CSA C22.2#60950-1 Issued:
2007/03/01 Ed:2 Information Technology Equipment Safety Part 1: General Requirements
WARRANTY
Warranty
Two year limited warranty covers parts and labor