AV15 INSTALLATION MANUAL | TruSteel AutoVap15 Installation Instructions | v. 1.3
34 / 43
•
The lower display shows the label with the alarm code; the upper display, if the alarm is
resettable, shows the label
rSt,
or
NO
if the alarm condition is still present.
SET
• Pressing SET with
rSt
present, will reset the alarm. Continue this through all alarms until it
is clear and the chiller is ready to start.
•
If you want to scroll through all alarms present, use up or down buttons
Alarm codes
CODE
DESCRIPTION Cause
Reset
Alarm trip
“AP” Alarms
Probe Fault
Bad probe
broken lead
Auto
Instantaneously
AEFL
Evaporator
Water level
alarm
Low water level Auto/ Manual
Delayed
ALc1
Phase Monitor
alarm
Wrong or
missing phase
Auto/ Manual
Instantaneously
b (n) HP
Compressor
(circuit number)
High pressure
Fan?
Condenser
Blocked
Manual
Instantaneously
b (n) LP
Compressor
(circuit number)
Low pressure
Low
temperature,
loss of
refrigerant
Auto/ Manual
Delayed
b (n) AC
Compressor
(circuit number)
freeze alarm
Low
temperature,
Low Flow
Auto/ Manual
Delayed
b1tF
Fan thermal
alarm
Fan jammed
(ice)
Manual
Instantaneously
C(n) tr
Compressor
(circuit number)
thermal alarm
Running at high
temperatures
Manual
Instantaneously
AEht
Evaporator inlet
high
temperature
High water
temperature
Manual
Instantaneously
b1AC Set Point
After the unit is primed, you need to lower the freeze point of the reservoir.
**Note: Contact MTA
to determine the PG ratio before adjusting the freeze alarm (b1AC) from set
point of 40F.
This will be based on the climate extremes for your chillerʼs location. For standard ambient
temperature above (32F) set the (b1AC) to 25F
To Lower freeze point follow the instructions below.
TURN UNIT TO STNBY TO ACCESS
Verify that the glycol percentage in the circulated coolant is adequate to protect the coolant from
freezing at the target outlet temperature. You must use Glycol and NOT water. Also consider the
minimum ambient air temperature if the chiller is to be installed outdoors. Adjust the glycol
percentage for the lowest of these temperatures with at a 10F safety factor below the freeze
alarm set point. For example, to operate at 25F coolant outlet temperature (indoors) set the
Содержание AV15
Страница 21: ...AV15 INSTALLATION MANUAL TruSteel AutoVap15 Installation Instructions v 1 3 21 43 ...
Страница 23: ...AV15 INSTALLATION MANUAL TruSteel AutoVap15 Installation Instructions v 1 3 23 43 2 RECOVERYASSEMBLY ...
Страница 26: ...AV15 INSTALLATION MANUAL TruSteel AutoVap15 Installation Instructions v 1 3 26 43 ASSEMBLY ...
Страница 42: ...AV15 INSTALLATION MANUAL TruSteel AutoVap15 Installation Instructions v 1 3 42 43 ...