Combustion air can be supplied to the stove in one of two ways.  Consult your local building code or CAN/
CSA-B365, or NFPA 211

1.  Direct outside air supply - (Necessary for mobile home installation, optional for residential installation.)  

• 

To draw outside air through the floor;  Attach the outside air adapter to the underside of the stove. Mark 
then cut or drill a 3"(76mm) diameter or larger hole in the floor under the adapter. This hole must get its 
air from a ventilated crawl space or be extended with duct to the outdoors (Figure 6 on page 15. or 
Figure 7 on page 16 

**If you are getting the intake air from a well ventilated crawl space, Connect the adapter to 3"(76mm) 
flexible or rigid metal venting passing thru the hole using into the ventilated space. Cover the inlet of the 
pipe with a 20GA wire mesh minimum rodent screen, and clamp in place.

**If you are extending the pipe thru to the outside, Install an approved 3"(76mm) inlet vent cap into the 
closest outside wall. Connect the stove's adapter to the Inlet vent through the hole using 3"(76mm) flex-
ible and/or rigid metal venting.  

• 

To draw air from behind the stove. Cut or drill a  corresponding hole in the closest exterior wall. Install an 
approved 3"(76mm) inlet vent cap. Attach the outside air adapter to the underside of the stove. Connect 
the adapter to the inlet vent cap using 3"(76mm) flexible and/or rigid metal venting. Provide water pro-
tection as required. 

2.  Room air supply - Remove the knockout or cover plate from the bottom of the Air box enclosure. The 

stove will now draw its air from the room through this opening and into the firebox intake

Note:  

The use of outside  combustion air for installation requires the unit to be secured to the structure to prevent 
dislodging of the air duct ("Securing Bracket Installation:" on page 13).

 

The living space around the heater must be well ventilated with good air circulation. Anything that may 
cause a negative pressure can cause gases or fumes to be pulled into the living area.  During extremely cold 
weather, and especially when burning at very slow rates, the upper parts of the exposed chimney may ice up, 
partially blocking the flue gases. If blockage occurs, flue gases may enter living space.

This unit is 

not

 designed to be operated with the firing door open. In addition to the obvious hazard of sparks 

landing on combustibles, an open fire door will cause the heater to draw air from the living space and possibly 
cause suffocation in an air tight home.

 Combustion Air 

Содержание TN10

Страница 1: ...restrictions and installation inspection requirements in your area IMPORTANT THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOMEOWNER SAVE THESE INSTRUCTIONS MODEL TN10 SERIAL TESTED and LISTED to CAN ULC...

Страница 2: ...26 Rating label location 26 HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTIL COOLED NEVER ALLOW CHILDREN TO TOUCH GLASS WARNING PLEASE SAVE THESE INSTRUCTIONS This manual describes the installatio...

Страница 3: ...s the energy required to vaporize the water in the fuel 3 The range of BTU outputs is based on efficiency using CSA B415 Performance testing of solid fuel burning heating appliances and burn rates fro...

Страница 4: ...pe requires only light pressure to seal This will prolong seal life It is important that the door seal be main tained in good condition Periodically inspect seals and replace if necessary Follow instr...

Страница 5: ...excessive corrosion burned out sections and exces sive warping Weekly Firebrick Visual for cracking Door Gasket sagging placement damage Monthly Brick rail tabs and brick rails Back side of air wash c...

Страница 6: ...he air inlet can be turned down substantially without excessive smoke generation Wood coals create very little creosote producing smoke 2 The cooler the surface over which the wood smoke is passing th...

Страница 7: ...imney Fire Have a fire extinguisher handy Contact your local municipal or state provincial fire authority for further information on how to handle a chimney fire It is most important that you have a c...

Страница 8: ...natural wood only Higher efficiency and lower emissions generally result when burning air dried seasoned hardwoods as compared to softwoods or to green or freshly cut hardwoods Wood should be properl...

Страница 9: ...eration after a good coal base exists and wood has charred Normal Operation WARNING This wood heater has a manufacturer set minimum low burn rate that must not be altered It is against federal regulat...

Страница 10: ...uring of the Paint Finish To achieve the best finish the paint on your stove must be baked on with small fires When burning your stove for the first 2 3 times it is very important that the room be wel...

Страница 11: ...ly after the following conditions have been met DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE DO NOT INSTALL IN A SLEEPING ROOM THIS ROOM HEATER MUST BE CONNECTED TO 1 A CHIMNEY...

Страница 12: ...proval U S NFPA 211 or CAN CSA B365 For for close clearances use a listed double wall connector See Figure 2 Double Wall Connector 2 Mobile Home installation must use listed double wall connector For...

Страница 13: ...2 51 mm beyond each side Securing Bracket Installation These will be needed to anchor the stove in a mobile home installation and are recommended when installing combustion air to prevent move ment of...

Страница 14: ...d location will not interfere with floor joists ceiling joists or rafters before proceeding further 4 As per the chimney manufacturer s instructions Cut a hole in the ceiling and roof to suit the chim...

Страница 15: ...ure specifcations for distance between vent termination heigth and chimney at roof line Also consult local building regulations The chimney may incorporate an offset To do this safely all sections of...

Страница 16: ...himney flue serving another appliance Minimum system height is 12 feet 3 0 m measured from top of appliance Fireclay Flue Liner Concrete Cap Chimney Approved Through Wall Installation 36 915mm Minimum...

Страница 17: ...DS OF MAINTAINING VAPOUR BARRIER System A Minimum 3 5 in 90 mm thick brick masonry wall framed into combustible wall with a minimum of 12 in 305 mm brick separation from clay liner to combustibles Fir...

Страница 18: ...ventilated air channels each 1 25 4 mm construction of sheet steel Chimney connector Masonry chimney constructed to NFPA 211 Chimney flue Minimum chimney clearance from masonry to sheet steel support...

Страница 19: ...66 m or as per chimney manufacturers roof clearances whichever is greater NOTE Longer chimney lengths and different pitch flashings may be used Install all components to the connector or chimney manu...

Страница 20: ...drill a corresponding hole in the closest exterior wall Install an approved 3 76mm inlet vent cap Attach the outside air adapter to the underside of the stove Connect the adapter to the inlet vent ca...

Страница 21: ...rse the process to replace the baffle assembly Installation 1 Insert one half of baffle board above the two back baffle tubes inside the firebox slide over to the right and allow to rest on the baffle...

Страница 22: ...10 2 Using the same 4 screws place the blower into the opening in the rear shield with the blower outlet pointing up Figure 11 3 Tighten the screws Blower Operation Proper blower speed matched with a...

Страница 23: ...s Install each side brick insert the brick under the retaining flange near the front of the baffle air box on each side of the firebox and then slide the brick to the back of the unit Next install 3 f...

Страница 24: ...See 1 2 3 above Low Heat Output 1 Wood is wet Use dry wood 2 Fire too small Build a larger fire 3 Draft too low Chimney plugged or restricted inspect and clean Won t Burn Overnight 1 Air control is s...

Страница 25: ...2pcs TN10 RP50987625 3 Baffle Tube Set 4pcs TN10 RP50001105 4 Door Casting Assy c w Handle TRNO DRBK 5 Door Gasket TN19 DGKIT 6 Replacement Glass c w gasket TRNO 7025 7 Glass Clamps 4 pcs TRNO 7608 8...

Страница 26: ...LES OFFICIELS DE LA CONSTRUCTION OU DE SERVICE D INCENDIE POUR DES INFORMATIONS QUANT AUX RES TRICTIONS PERMIS D INSTALLATION ET INSPECTIONS DANS VOTRE R GION NE RELIEZ PAS CET APPAREIL UN CONDUIT DE...

Страница 27: ...5055 549 A TN10 NA 080617 28 27...

Страница 28: ...Web site www truenorthstoves com 2975 Allenby Rd Duncan BC V9l 6V8 2017 Copyright Pacific Energy Fireplace Products LTD Reproduction adaptation or translation without prior written permission is proh...

Отзывы: