Connecting to a masonry chimney
Ensure that the chimney is in good condition and meets local building codes. Your stove may work better if
the chimney is fully lined with a stainless steel liner, this is because the liner will retain heat and promote draft.
The chimney flue or liner should be the same size as the stove outlet for optimal performance. Reducing or
increasing the flue size may adversely affect stove performance. Chimney flue exit is to be 3 feet (1 m.) above
the roof and two feet (0.6 m.) above highest projection within 10 feet (3 m.). The installation must meet all
local codes. Do not connect this unit to a chimney flue serving another appliance. Minimum system height is
12 feet (3.0 m.) (measured from top of appliance).
Fireclay Flue Liner
Concrete Cap
Chimney
Approved Through
Wall Installation
36” (915mm)
Minimum
Minimum Ceiling
Height 5’ (1.52 m)
48”
(1219 mm)
Non-combustible
Ember Protector
Hooded vent or 90°
elbow turned down.
Chimney
Connector
Ensure that the Masonry chimney
meets all National Fire Protection
Association and local building codes.
Have the chimney cleaned and
inspected by a professional to ensure
there are no cracks, weak mortar or
other signs of deterioration. See pipe
manufactuers installation instructions
for further information
* 3"(76mm) diameter air inlet with rodent screen
* If the crawl space is well ventilated it is not necessary
to extend air inlet to outside
Combustibles
in front of the
unit
Figure 7: TN10 Venting to a masonry chimney.