8 TX6356-UM-EN-01
Menu configuration
•
Security code protection
•
Setpoint level and mode adjustment
•
Data output protocol configuration
•
Flow units selection
•
Duty display text entry
Fault indication
•
Loss of communications
•
Sensing module absent
•
Sensor over-range
1.6 Electrical Details
0.4 to 2 V Output Signal - 3/4 wire - remote powered
Supply voltage
Group 1
10 to 14 V dc
Minimum line load
Group 1
10 K ohms
Supply current
Group 1
20 mA @ 12 V dc
4 to 20 mA Output Signal - 3/4 wire - remote powered
Supply voltage
Group 1
10 to 14 V dc
General Purpose
18 to 28 V dc
Maximum line load
Group 1
220 ohm at 12 V dc
General Purpose
500 ohm at 24 V dc
Supply current
Group 1
48 mA @ 12 V dc
General Purpose
40 mA @ 24 V dc
5 to 15 Hz Output Signal - 3/4 wire - remote powered
Supply voltage
Group 1
10 to 14 V dc
Maximum line load
Group 1
Opto isolated to 2 mA
maximum
Supply current
Group 1
20 mA @ 12 V dc