background image

Thermostatic electric shower

5

table B

Note: 

Cable selection is dependent on 

derating factors

Twin and earth PVC insulated cable

Current carrying capacity

In conduit

trunking

6 mm²

38A

10 mm²

52A

16 mm²

69A

Installed in an 

insulated wall

6 mm²

35A

10 mm²

47A

16 mm²

63A

Clipped direct

or buried in a 

non-insulated 

wall

6 mm²

47A

10 mm²

64A

16 mm²

85A

E-002-A

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 
protection must conform with BS 7671 (IEE 
wiring regulations) and be sufficient for the 
amperage required.
The following notes are for guidance only:

1

 

The shower must only be connected to a 
230-240V ac supply. If you are installing a 
shower with a kilowatt rating above 9kW, it 
is advisable to contact the local electricity 
supply company.

1.1

  The electrical rating of the shower is shown 

on the rating label 

(Fig.3)

 within the unit.

2

 

 Before making any sort of electrical 
connection within the installation make sure 
that no terminal is live. If in any doubt, 
switch off the whole installation at the mains 
supply and remove the correct fuse.

3

 

The shower must be connected to its own 
independent electrical circuit. IT MUST NOT 
be connected to a ring main, spur, socket 
outlet, lighting circuit or cooker circuit.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

 

Check your consumer unit (main fuse box) 
has a main switch rating of 80A or above 
and that it has a spare fuse way which will 
take the fuse or Miniature Circuit Breaker 
(MCB) necessary for the shower 

(Fig.4).

4.1

  If your consumer unit has a rating below 

80A or if there is no spare fuse way, then the 
installation will not be straightforward and 
may require a new consumer unit serving 
the house or just the shower.

4.2

  You will need to contact the local electricity 

company. They will check the supply and 
carry out what is necessary. 

5

 

For close circuit protection DO NOT use a 
rewireable fuse. Instead use a suitably rated 
Miniature Circuit Breaker (MCB) or cartridge 
fuse 

(see Table A).

5.1

  A 30mA residual current device (RCD) must 

be installed in all UK electric and pumped 
shower circuits. This may be part of the 
consumer unit or a separate unit.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

  The switch must be accessible and clearly 

identifiable, but out of reach of a person 
using a fixed bath or shower, except for the 
cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily 
accessible to switch off after using the 
shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B).

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the 

disconnection time and thermal constraints 
which means that for any given combination 
of current demand, voltage drop and cable 
size, there is a maximum permissible circuit 
length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed in 
areas where the ambient temperature is 
above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

 

In the majority of installations, the cable 
will unavoidably be placed in one or more 
of the above conditions. This being so, it 
is strongly recommended to use a 
minimum of 10mm cabling throughout 
the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

E-002-A

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 
protection must conform with BS 7671 (IEE 
wiring regulations) and be sufficient for the 
amperage required.
The following notes are for guidance only:

1

 

The shower must only be connected to a 
230-240V ac supply. If you are installing a 
shower with a kilowatt rating above 9kW, it 
is advisable to contact the local electricity 
supply company.

1.1

  The electrical rating of the shower is shown 

on the rating label 

(Fig.3)

 within the unit.

2

 

 Before making any sort of electrical 
connection within the installation make sure 
that no terminal is live. If in any doubt, 
switch off the whole installation at the mains 
supply and remove the correct fuse.

3

 

The shower must be connected to its own 
independent electrical circuit. IT MUST NOT 
be connected to a ring main, spur, socket 
outlet, lighting circuit or cooker circuit.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

 

Check your consumer unit (main fuse box) 
has a main switch rating of 80A or above 
and that it has a spare fuse way which will 
take the fuse or Miniature Circuit Breaker 
(MCB) necessary for the shower 

(Fig.4).

4.1

  If your consumer unit has a rating below 

80A or if there is no spare fuse way, then the 
installation will not be straightforward and 
may require a new consumer unit serving 
the house or just the shower.

4.2

  You will need to contact the local electricity 

company. They will check the supply and 
carry out what is necessary. 

5

 

For close circuit protection DO NOT use a 
rewireable fuse. Instead use a suitably rated 
Miniature Circuit Breaker (MCB) or cartridge 
fuse 

(see Table A).

5.1

  A 30mA residual current device (RCD) must 

be installed in all UK electric and pumped 
shower circuits. This may be part of the 
consumer unit or a separate unit.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

  The switch must be accessible and clearly 

identifiable, but out of reach of a person 
using a fixed bath or shower, except for the 
cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily 
accessible to switch off after using the 
shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B).

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the 

disconnection time and thermal constraints 
which means that for any given combination 
of current demand, voltage drop and cable 
size, there is a maximum permissible circuit 
length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed in 
areas where the ambient temperature is 
above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

 

In the majority of installations, the cable 
will unavoidably be placed in one or more 
of the above conditions. This being so, it 
is strongly recommended to use a 
minimum of 10mm cabling throughout 
the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Содержание Topaz T100si

Страница 1: ...INSTALLERS PLEASE NOTE THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER 2180360p November 2011 Topaz T100si thermostatic control electric shower Installation and operating instructions...

Страница 2: ...he cover 13 Operating the shower 14 Operating functions 17 Cleaning 19 Instructions for installers and service engineers only 20 21 Spare parts 22 23 Fault finding 24 25 Guarantee service policy etc r...

Страница 3: ...unit will result in higher temperatures and could also cause the PRD Pressure Relief Device in the unit to operate 1 9 This product is not suitable for mounting into steam rooms or steam cubicles 2 P...

Страница 4: ...ied person and in the sequence of this instruction book Care taken during the installation will provide a long trouble free life from your shower SPECIFICATIONS Electrical Nominal power Nominal power...

Страница 5: ...Earth connection 10 PRD 11 Solenoid valve 12 Trimplate 13 Thermostatic valve 14 Scale trap 15 Pressure switch 16 Shower outlet 17 Guide pockets Inside cover fig 2 18 Control printed circuit board 19 S...

Страница 6: ...re fuse way which will take the fuse or Miniature Circuit Breaker MCB necessary for the shower Fig 4 4 1 If your consumer unit has a rating below 80A or if there is no spare fuse way then the installa...

Страница 7: ...8 The current carrying capacity of the cable must be at least that of the shower circuit protection see Table B 8 1 To obtain full advantage of the power provided by the shower use the shortest cable...

Страница 8: ...ult a competent plumber Under site conditions where the power supply is below 220 volts and the mains water pressure is above 5 bar it is recommended to fit a pressure reducing valve set at 3 5 bar A...

Страница 9: ...ich has an optimum viewing angle that is slightly below eye level Therefore position the unit so the display is at nose level For multiple users of varying heights an optimum shower height must be arr...

Страница 10: ...shower is positioned over a bath or shower tray because if the PRD operates then water will eject from the bottom of the unit Should this happen turn off the electricity and water supplies to the show...

Страница 11: ...from the rear or bottom the centre of the inlet valve to the wall surface is 21 mm fig 10 Note If entry is from the rear the nut of the compression fitting will be partially behind the surface of the...

Страница 12: ...ff the water supply either at the mains stopvalve or the isolating stopvalve Connect the mains water supply to the inlet fig 12 of the shower via 15 mm copper stainless steel or plastic pipe using a 1...

Страница 13: ...routing through conduit or in trunking or by embedding in the wall in accordance with current IEE regulations The use of connections within the unit or other points in the shower circuit to supply pow...

Страница 14: ...o position so that the control spindle locates correctly the flats only allow the spindle and knob only fit one way Should any difficulty arise recheck the points above While applying slight pressure...

Страница 15: ...sure the pipe and cable entering the unit do not prevent the cover locating correctly to the backplate d Make sure the valve spindle has the flat and keyway slot uppermost 12 o clock position e Make s...

Страница 16: ...lay shows FUL fig 20 indicating full power is being used After a few seconds two up arrows start flashing indicating the unit is working towards its preset showering temperature fig 21 This is achieve...

Страница 17: ...the same temperature as before Note If the setting was high at full power then it will not be possible to obtain the same temperature on economy power The shower will try to provide the highest tempe...

Страница 18: ...fig 27 position all inner segments full that corresponds to the control position To decrease the shower temperature Turn the temperature control anti clockwise the current temperature display is repla...

Страница 19: ...ean the showerhead or not The shower will then reset automatically for a further preset number of shower operations before flashing the reminder again Low pressure When the display backlight turns red...

Страница 20: ...e of the fault and replace the safety device once the unit has been repaired Changing the fascia This shower unit has the facility for the coloured fascia to be simply changed for another colour of yo...

Страница 21: ...y affect the product surface finish and invalidate your guarantee It is important to keep the showerhead clean to maintain the performance of the shower The hardness of the water will determine the fr...

Страница 22: ...son Switch off the electricity supply at the mains Remove the cover The inlet filter is situated in the solenoid inlet fig 54 and can be removed to clean To gain access to the filter will require the...

Страница 23: ...omplete with O rings Be aware of water discharging as the heater can exhausts Clean out the trap and remove all sediment Flush the can through by leaving the cap off and switching on the power at the...

Страница 24: ...or 9 5kW 22010310 Restrictor 10 5kW 22010410 5 Solenoid valve assembly and O ring 83307110 6 Pressure Relief Device 82800450 7 Trimplate 7052989 8 Can brace 7053008 9 Thermostatic valve and O rings 4...

Страница 25: ...set 2 x earth 1 x solenoid wires 83307150 Power PCB carrier 7052991 Rubber microswitch cover 7063046 Inlet filter 7053009 16 Coloured fascias Seaspray TSTZFSEA Aqua TSTZFAQU Azure TSTZFAZU Lilac TSTZF...

Страница 26: ...Unit malfunction 2 2 1 Contact Customer Service 3 Water too hot 3 1 Temperature control incorrect setting 3 1 1 Turn anti clockwise 3 2 Unit malfunction 3 2 1 Contact Customer Service 4 Unstable show...

Страница 27: ...or flashing 6 4 Blocked connecting tube to pressure switch 6 4 1 Make sure the tube from solenoid valve to pressure switch is not kinked or blocked 7 Water continues to flow when unit is isolated at i...

Страница 28: ...umber and power rating of the product together with the date of purchase and where applicable details of the particular fault 2 If required the Customer Service Advisor will arrange for a qualified en...

Страница 29: ...Showers Power Showers Smart Showers Shower Towers From Top Shower Brands Mira Showers Aqualisa Showers Triton Showers Gainsborough Showers Shower Pumps can upgrade your showering experience even more...

Отзывы: