background image

43

TriStar MPPT Operator’s Manual

42

Operation

Equalize Time-out

1:00

2:00

3:00

4:00

5:00

6:00

Absorp. V

Bulk

Float

Equalize

Equalize timeout

time (hrs)

Equalize V

Figure 4-6. Equalize timeout charging profile

The charging profile in figure 4-6 shows an 

Equalize Timeout

 event. The timeout timer begins as 

soon as battery voltage exceeds the Absorption voltage setpoint. If there is insufficient charging 

current or system loads are too large, the battery voltage may not reach the Equalize setpoint. 
Equalize Timeout is a safety feature that prevents high battery voltage for extended periods of 
time which may damage the battery.

Temperature Compensation

All charging settings are based on 25°C  (77°F).  If the battery temperature varies by 5°C, the 
charging setting will change by 0.15 Volts for a 12 Volt battery.  This is a substantial change in 
the charging of the battery, and the use of the Remote Temperature Sensor (RTS) is recom-
mended to adjust charging to the actual battery temperature.  

The need for temperature compensation depends on the temperature variations, battery type, 
how the system is used, and other factors.  If the battery appears to be gasing too much or not 
charging enough, the RTS can be added at any time after the system has been installed.  See 
Section 2.3 - Step 4 for installation instructions.

Battery Sense

Voltage drops are unavoidable in power cables that carry current, including the 
TriStar MPPT 150V battery cables.  If Battery Sense wires are not used, the controller must use 
the voltage reading at the battery power terminals for regulation. Due to voltage drops in the 
battery cables, the battery power connection voltage will be higher than the actual battery bank 
voltage while charging the battery.

Two sense wires, sized from 1.0 to 0.25 mm

2

 (16 to 24 AWG), can be used for battery voltage 

sense.  Because these wires carry no current, the voltage at the TriStar will be identical to the 
battery voltage.  A 2-position terminal is used for the battery sense connection.
Generally accepted wiring practice is to limit voltage drops between the charger and the battery 
to 2%. Even properly sized wiring with 2% drop can result in a 0.29 Volt drop for 14.4V charg-
ing (or 1.15 Volt for a 48 Volt nominal system). Voltage drops will cause some undercharging of 

the battery.  The controller will begin Absorption or limit equalization at a lower battery voltage 
because the controller measures a higher voltage at the controller’s terminals than is the actual 
battery voltage.  For example, if the controller is programmed to start Absorption at 14.4V, when 
the controller “sees” 14.4V at its battery terminals, the true battery voltage would only be 14.1V if 
there is a 0.3V drop between the controller and battery.

Note that the battery sense wires will not power the controller, and the sense wires will not com-
pensate for losses in the power wires between the controller and the battery.  The battery sense 
wires are used to improve the accuracy of the battery charging.

See Section 3.2 - Step 7 for instructions on how to connect the battery sense wires.

4.3 Push-button

The following functions can be enabled with the push-button (located on the front cover):

PUSH

•  Reset from an error or fault.

•  Reset the battery service indication if this has been activated in custom settings.  A new 

service period will be started, and the flashing LEDs will stop blinking.  If the battery ser

-

vice is performed before the LEDs begin blinking, the push-button must be pushed at the 
time when the LEDs are blinking to reset the service interval and stop the blinking. 

PUSH AND HOLD 5 SECONDS

•  Request battery equalization manually.  The TriStar MPPT 150V will begin equalization 

in either the manual or automatic equalization mode. Equalization will begin when there 

is sufficient solar power to charge the battery up to the equalization voltage.  The LEDs 

will blink the sequence defined in table 4-3 below to confirm that an equalize has been 

requested. The equalization request will automatically stop per the battery type selected 
(see Section 4.4). Equalization will only occur if the selected battery type has an equaliza-
tion stage.

•  Stop an equalization that is in progress.  This will be effective in either the manual or 

automatic mode.  The equalization will be terminated. The LEDs will blink to confirm the  

equalize has been cancelled as shown in table 4-3 below.

Push-button Action

SOC LED Indication*

Manual Equalization Started

Green / Yellow / Red  - Green / Yellow / Red - Green - Green

Stop Equalization

Green / Yellow / Red  - Green / Yellow / Red  - Red - Red

           Table 4-3. Manual equalization LED indications

      *  See key on p. 44

NOTE:  
For multiple TriStar MPPT 150V controllers on a MeterBus

TM

 network, initialize a battery 

equalization using the TriStar meter so that all controllers are synchronized.

Содержание TS-MPPT-30

Страница 1: ...ng System Controller www morningstarcorp com Solar Battery Charger With TrakStarTM Maximum Power Point Tracking Technology MODELS TS MPPT 30 TS MPPT 45 TS MPPT 60 TRISTAR MPPT TM For the most recent m...

Страница 2: ...Controller Installation 18 4 0 Operation 34 4 1 TrakStarTM MPPT Technology 34 4 2 Battery Charging Information 36 4 3 Push button 43 4 4 LED Indications 44 4 5 Protections Faults Alarms 46 4 6 Inspect...

Страница 3: ...ht to avoid excessive heating from a loose connection Use properly sized conductors and circuit interrupters The grounding terminal is located in the wiring compartment and is identified by the symbol...

Страница 4: ...yst me et d application CAUTION Do not open or mutilate batteries Released electrolyte is harmful to skin and may be toxic PRUDENCE Ne pas ouvrir ou mutiler les piles L lectrolyte est nocif pour la pe...

Страница 5: ...unettes de protection et ayez de l eau fra che disposition en cas de contact avec l lectrolyte Enlevez les montres bagues bijoux et autres objets m talliques avant de travailler avec des piles Porter...

Страница 6: ...urement Please take the time to read this operator s manual and become familiar with the controller This will help you make full use of the many advantages the TriStar MPPT 150V can provide for your P...

Страница 7: ...2 29 battery chargers A means shall be provided to ensure all pole disconnection from the power supply This discon nection shall be incorporated in the fixed wiring Using the TriStar MPPT 150V ground...

Страница 8: ...enables the TriStar MPPT 150V to control external devices Four 4 relay control ports can be configured in various combinations to perform the following tasks generator control 2 3 and 4 wire configur...

Страница 9: ...ements are noted on occasion for convenience however the installer should have a complete understanding of NEC and UL requirements for photovoltaic installations Installation 3 0 Read through the enti...

Страница 10: ...through conduit or wire glands Table 3 1 below pro vides the knockout sizes and quantity on the TriStar MPPT 150V wiring box Knockout locations and dimensions are on the inside front cover Quantity T...

Страница 11: ...hole on the TriStar MPPT 150V with the screw head Slide the TriStar MPPT 150V down over the keyhole 7 Check for vertical plumb with a level 8 Mark two 2 mounting hole locations in the wiring box 9 Rem...

Страница 12: ...charges when the controller is con figured for automatic equalizations settings switch 7 Switch 7 Battery Equalization Choose between manual and automatic battery equalization charging In the manual...

Страница 13: ...RTS peut tre raccourci si la totalit de la longueur n est pas n cessaire Assurez vous de r installer la bobine en ferrite sur l extr mit du RTS si une longueur de c ble est enlev e Cette bobine assure...

Страница 14: ...rsed sense voltage Connecting the voltage sense wires to the RTS terminal will cause an alarm If a TriStar meter is installed check the TriStar Settings to confirm the Voltage Sense and the RTS if ins...

Страница 15: ...the connection of array terminals The battery positive terminal has a red cover the solar positive terminal has a yellow cover REMARQUE Pour la conformit CNE le TriStar MPPT 150V doit tre install sel...

Страница 16: ...des tensions de circuit ouvert sup rieures 150 Vdc la lumi re du soleil V rifiez que le coupe circuit ou l interrupteur d entr e solaire a t ouvert d connexion avant d installer les c bles du syst me...

Страница 17: ...TISSEMENT Risque d endommagement La connexion du r seau solaire sur la borne de la batterie endommagera le TriStar MPPT 150V de fa on permanente AVERTISSEMENT Risque d endommagement La connexion du r...

Страница 18: ...uit voltage Voc rating will not exceed the TriStar MPPT 150V 150 Volt maximum input voltage rating at worst case coldest module temperature The solar module documentation should provide Voc vs tempera...

Страница 19: ...the battery from long term overcharge The green SOC LED will blink once every two 2 seconds during Float charging Once in Float stage loads can continue to draw power from the battery In the event tha...

Страница 20: ...f the battery is fully recharged However a solar charged battery is seldom completely recharged so the soft lead sulfate crystals harden over a period of time Only a long controlled overcharge or equa...

Страница 21: ...ded to the normal Absorption duration Float Time out Figure 4 4 Float exit time out charging profile After entering Float stage the controller will only exit Float if the battery voltage remains below...

Страница 22: ...attery The controller will begin Absorption or limit equalization at a lower battery voltage because the controller measures a higher voltage at the controller s terminals than is the actual battery v...

Страница 23: ...R Battery service is required all three LEDs blinking until service is reset battery service notification is only enabled in custom settings or when any custom edit is programmed Battery Status Gener...

Страница 24: ...working properly Battery Voltage Sense Failure G R sequencing with constant yellow If a fault in the battery sense connection such as a short circuit open circuit or loose terminal occurs after the ba...

Страница 25: ...ce Battery Sense Out of Range Disconnected A battery sense wire is disconnected Inspect the battery sense connections This alarm is set when the voltage at the battery sense voltage differs by more th...

Страница 26: ...eously Table 5 1 below provides a summary of supported features for each communication interface MeterBus RS 232 EIA 485 Ethernet Display system network data on a TriStar meter Connect a TSMPPT to a R...

Страница 27: ...five 5 controllers can be networked together with a single hub Multiple hubs can be daisy chained together to allow networks of up to 14 controllers and a meter Refer to the HUB 1 and TriStar Meter ma...

Страница 28: ...nnect the TriStar MPPT 150V to other Morningstar controllers with the RSC 1 Serial to EIA 485 Adapter sold separately bridge an Ethernet connection through a TriStar MPPT 150V to an EIA 485 network Th...

Страница 29: ...for both scenarios is shown in figure 5 3 below Ethernet Cross over Cable Figure 5 3 Ethernet network diagrams Factory Default Network Settings DHCP enabled Live View Web Address http tsmppt serial nu...

Страница 30: ...ST BETWEEN ALL TERMINALS AND GROUND BEFORE TOUCHING AVERTISSEMENT RISQUE DE CHOC LETRIQUE NON ALIMENTATION OU AUX BORNES D ACCESSOIRES SONT ISOL S LEC TRIQUEMENT DE L ENTR E DE C C ET DOIT TRE ALIMENT...

Страница 31: ...not work Power is supplied to the 4 wire bus on the Power Ground lines The bus requires voltage in the range 8 16 Vdc All bus connections are secure and each terminal is wired in parallel line A to li...

Страница 32: ...Voltage All 150 Volts dc Battery Operating Voltage Range All 8 72 Volts dc Nominal Maximum Input Power 12 Volt 400 Watts 600 Watts 800 Watts 24 Volt 800 Watts 1200 Watts 1600 Watts 48 Volt 1600 Watts...

Страница 33: ...terminals Minimum wire size 0 25 mm2 24 AWG Maximum wire size 1 0 mm2 16 AWG Recommended torque 0 40 Nm 3 5 in lb Knockouts trade sizes M20 1 2 1 1 1 4 Mounting Vertical surface Environmental Operatin...

Страница 34: ...ter TriStar MPPT 24 Volt Efficiency output power Watts efficiency 99 98 97 96 95 94 93 92 91 90 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 0 89 33 Vmp 66 Vmp 98 Vmp 26 Vmp Batte...

Страница 35: ...t 30 C ambient temperature Ampacity for not more than three current car rying conductors in a raceway cable or earth buried 2 Voltage Drop Charts for 75 C Solid Copper Wire 1 Way Wire Distance feet 12...

Страница 36: ...at 30 C ambient temperature Ampacity for not more than three current car rying conductors in a raceway cable or earth buried 2 Voltage Drop Charts for 90 C Solid Copper Wire 1 Way Wire Distance feet 1...

Страница 37: ...005 EMC Immunity Industrial Environments EN 55022 2007 Class B EMC Emissions EN 60335 1 2002 Safety EN 60335 2 29 2005 Safety IEC 62109 1 2010 Safety of Power Converters in PV Systems TrisStar MPPTTM...

Отзывы: