33
TriStar MPPT Operator’s Manual
32
Installation
WARNING: Risk of Damage
Be very certain that the solar connection is made with correct polarity. Turn on
the solar array breaker/disconnect and measure the voltage on the open wires
BEFORE connecting to the TriStar MPPT 150V. Disconnect the solar breaker/
disconnect before wiring to the controller.
AVERTISSEMENT : Risque d’endommagement
Assurez-vous que la connexion solaire est effectuée avec la polarité correcte.
Activez le coupe-circuit/interrupteur de réseau solaire et mesure la tension sur
les câbles ouverts AVANT la connexion au TriStar MPPT 150V. Déconnectez le
coupe-circuit/interrupteur solaire avant le câblage sur le contrôleur.
6. Connect the Solar + (positive) wire to the Solar + terminal on the TriStar MPPT 150V. The
Solar + terminal has a yellow cover.
7. Connect the Solar - (negative) wire to one of the Common Negative terminals on the
TriStar MPPT 150V.
Torque all four (4) power terminals to 50 in-lbs (5.65 Nm)
Power-up
WARNING: Risk of Damage
Connecting the solar array to the battery terminal will permanently damage the
TriStar MPPT 150V.
WARNING: Risk of Damage
Connecting the solar array or battery connection with reverse polarity will
permanently damage the TriStar MPPT 150V.
AVERTISSEMENT : Risque d’endommagement
La connexion du réseau solaire sur la borne de la batterie endommagera le
TriStar MPPT 150V de façon permanente
.
AVERTISSEMENT : Risque d’endommagement
La connexion du réseau solaire ou la connexion de la batterie avec une polarité
inversée endommagera le TriStar MPPT 150V de façon permanente.
•
Confirm that the Solar and Battery polarities are correct.
•
Turn the battery disconnect switch on first. Observe that the LEDs indicate a successful
start-up. (LEDs blink Green - Yellow - Red in one cycle)
• Note that a battery must be connected to the TriStar MPPT 150V to start and operate the
controller. The controller will not operate only from solar input.
• Turn the solar disconnect on. If the solar array is in full sunlight, the TriStar MPPT 150V
will begin charging. If an optional TriStar Meter is installed, charging current will be report-
ed along with charging state.
To
Power-down
WARNING: Risk of Damage
ONLY disconnect the battery from the TriStar MPPT 150V AFTER the solar input has
been disconnected. Damage to the controller may result if the battery is removed
while the TriStar MPPT 150V is charging.
AVERTISSEMENT : Risque d’endommagement
Le TriStar MPPT 150V SEULEMENT déconnecter la batterie APRÈS l’entrée solaire a
été déconnectée. Le contrôleur pourrait endommager si la batterie est retirée quand le
TriStar MPPT 150V est en charge.
• To prevent damage, power-down must be done in the reverse order as power-up.