
Monopack 2 Manual V1.04
9
Copyright © 2010, TRINAMIC Motion Control GmbH & Co. KG
2.8
The Step/Direction input socket
The Step/Direction input socket provides the same differential step/direction inputs as the 25-pin Sub-D socket. It is
electrically identical with those inputs.
2.9
The hexadecimal Switch
This switch is used to set the LSN of the CAN receive identifier and the RS485 address. If the switch is set to zero,
the CAN receive identifier and the RS485 address will be reset to 1 and the CAN send identifier will be reset to 2
(please see also section 3.2.2, 4.7.2 and 4.7.3). The position of the hexadecimal switch is only read after a hardware
reset. So it is required to power off the unit when changing the hexadecimal switch setting.
2.10
The DIP switches
The DIP switches allow selecting the interface that is to be used and the operating mode. They have the following
functions:
Switch Function
1
OFF: Use RS485 interface; ON: Use CAN interface
2
OFF: Use RS485 interface; ON: Use CAN interface
3
OFF: Use CAN interface; ON: Use RS485 interface
4
OFF: Use CAN interface; ON: Use RS485 interface
5
OFF: Use Monopack 2 (binary) command set (compatible with old Monopack)
ON: Use Monopack LT (ASCII) command set (compatible with old Monopack LT)
6
OFF: normal operation
ON: perform a firmware upgrade
7
OFF: No bus termination
ON: 100 Ohms RS485/CAN bus termination
8
OFF: Maximum current is 2.5A (compatible with Monopack / Monopack LT)
ON: Maximum current is 5.7A
Please note that switches 5 and 6 are only read after a hardware reset. So it is necessary to power off the unit
when changing the settings of switch 5 or 6.