37
Note:
Before taking any corrective action, always positively identify the real source of the odour. Check
if the odour is coming from another outside source such as a storm drain. All Tricel Novos
’
vent
gases back through soil pipe and out roof vents. Improperly installed roof vents can cause odour
problems. Traps in drains prevent odours from entering the home. To function, they must contain
water and be sealed correctly.
10.2
Odours
Symptom
Possible causes
Solution
Effluent odour directly
outside the house or
inside the house
Pipe connections to toilets
or drains not connected
correctly.
Check that the traps / U - bends in the drains
are fitted and the joints sealed.
An air vent on pipe-work
not fitted or fitted
incorrectly.
Ensure all effluent pipes are vented correctly,
vents are normally fitted to all pipes, and they
should be higher than the eve of the roof.
Pipe work is damaged or
blocked or fitted
incorrectly.
Inspect pipe work to ensure it is undamaged and
clear of obstructions or sagging.
Bad effluent odour
directly over the tank
Pipe work to or from the
tank is blocked.
Check the level of liquid in the tank. Ensure the
pipes are not blocked and are fitted correctly to
the tank.
Chemical kill of bacteria.
Ensure pumps are working properly (If
applicable). If the symptom persists for 48
hours or more, remove all liquid and replace
with clean water.
No air delivery -
Hydraulic/Organic is
overloading the tank vent.
Check blower is functioning properly
Note:
Smoke bombs/pellets, available from a plumber’s merchants, can be used to
trace the source the odour.
In accordance with our normal policy of product development, this specification is subject to change
without notice. (December 2017)
11
Certification
The Tricel Novo has successfully passed stringent European testing and is approved to the new
European standard EN 12566-3 Small wastewater treatment plants for up to 50 PT-Part 3: Packaged
and/or site assembled domestic wastewater treatment plants. The Tricel Novo was placed through a
rigorous 38-week test, by the certified laboratory PIA GmbH-Testing Institute for wastewater
technology in Aachen, Germany
The Tricel Novo passed all structural testing (crush test & durability test) carried out by PIA staff.
Water tightness tests were performed by PIA at our headquarters on the range of tanks up to 50PE
and successfully passed all of the required tests.
Содержание Novo UK10
Страница 1: ...0 106 Rev 11 Dec 2017 Tricel Novo UK6 50 Wastewater Treatment Plants Engineering a green future...
Страница 4: ...3...
Страница 5: ...4...
Страница 10: ...9...
Страница 11: ...10...
Страница 26: ...25 5 11 1 Electrical Diagrams 5 11 1 1 Tricel Novo Gravity Outlet UK6 UK8 UK10 UK12 Control Panel No 209102...
Страница 27: ...26 UK18 UK24 Control Panel No 209116...
Страница 28: ...27 UK30 UK36 UK42 UK50 Control Panel No 209111...
Страница 29: ...28 5 11 1 2 Tricel Novo Pumped Outlet UK6 UK8 UK10 UK12 UK18 UK24 Control Panel No 209101...
Страница 30: ...29 UK30 UK36 UK42 UK50 Control Panel No 209112...
Страница 42: ...41 12 Terms conditions Subject to our standard terms and conditions which are available on request...
Страница 43: ...42...