Installation
Mounting and wiring
3
1
/
8
”
4
3/8
”
1
/
8
DIA (typ 4 places)
3
/
8”
DIA
1
1
/
2
”
Figure 3: Vortex sensor mounting location
The VMS-1655M incorporates two analog output signals, one is a 0 VDC to 10 VDC actuator control output for controlling the Flow Safe
Vortex II baffles and the other is a 4 mA to 20 mA output for monitoring hood exhaust air flow remotely. These factory- calibrated analog
signals are available at the vortex sensor connector. The VMS-1655M is also capable of being directly monitored by the BMS over the
BACnet MS/TP RS485 port (CN7) located at back of the VMS-1655M touchscreen display. See page 17 for BACnet object list.
Note:
While the VMS-1655M model is calibrated and programmed at the factory with default settings for fume hood applications, a final
calibration of face velocity is required following installation.
Installation
Correct location of the vortex sensor is crucial for obtaining the best possible operation of the VMS-1655M. The system measures
the internal negative pressure of the fume hood to accurately determine the face velocity at the sash opening. The sensor must be
located in a position that is least affected by turbulent air within the fume hood. See Figure 10.
See Figure 9 and Figure 10 for dimensions and suggested mounting arrangements of the flow sensor on the fume hood.
Note:
Be certain that sensor reference port is in laboratory room air. If necessary to obtain this, use the louvered mounted on exterior
panel of the fume hood.
See Figure 10 for mounting details for the VMS-1655M touchscreen display unit. The preferred location is eye-level, usually on one of
the side bezel panels. Please note that the display unit is cable connected to the vortex sensor module, and provisions must be made
to route the cable without interference with the fume hood sash or sash cable.
Note:
Remove red cap from sensor after installation.
To monitor the VMS-1655M over a BACnet MS/TP BAS network, connect the VMS-1655M touchscreen display to the BMS via the CN7
terminal block located on back of display board. Make sure to observe correct polarity of RS485 connection.
Connect the interface cable between the vortex sensor and the touchscreen display before applying power to the system.