VMS-1655M
LIT-12013297
4
Red
/ 24 VAC / 30VA
connected to the VMS
Ground
}
}
120 VAC
50/60 Hz
Black
White
Only
Class 2
wiring in
this compartment
}
240 VAC
50/60 Hz
Blue
Slow Blow
Fuse
Transformer
50/60 Hz
Note:
I
nstall this product with the manufacturer provided isolated power supply and connect to an electrical circuit protected by a
minimum 20A circuit breaker. Mount this circuit breaker in an approved electrical enclosure located separately, but in close proximity, to
this product.
Isolated power supply
Figure 2: Stepdown isolation transformer, provided with the VMS-1655M
Risk of Property Damage
Do not use a single transformer to power both the actuator and the controller. Use a 24 VAC 30 VA Class 2, Limited Energy, or
LPS for the controller, and a separate 24 VAC 20 VA Class 2, Limited Energy, or LPS for the actuator. Failure to follow the wiring
diagrams may result in damage to the actuator, the transformer, the controller, or all devices and could void your warranty.
Note:
The Actuator is sold separately.
Risque de dommage à la propriété
N’utilisez pas un seul transformateur pour alimenter à la fois l’actionneur et le régulateur. Utilisez un transformateur de classe 2
à 24 V CA 30 VA, à limitation d’alimentation ou LPS pour le régulateur et un transformateur de classe 2 à 24 V CA 20 VA à
limitation d’alimentation ou LPS séparé pour l’actionneur. Ne pas respecter les schémas de câblage peut causer des dommages à
l’actionneur, le transformateur, le régulateur ou tous les appareils et peut annuler votre garantie.
Remarque :
L’actionneur est vendu séparément.