VMS-1655M
LIT-12013297
16
Technical specifications
1.
NIST Traceable/Individual certification available as an option.
2. Accuracy is ±5 FPM when velocity drops below 60 FPM or exceeds 140 FPM.
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond
these specifications, consult your local Triatek representative. Johnson Controls shall not be liable for damages resulting from
misapplication or misuse of its products.
Electrical
Face velocity range
0 fpm to 600 fpm
Accuracy of measurement
± 2 fpm, Accuracy is ± 5 fpm when velocity drops below 60 fpm or
exceeds 140 fpm. Configure maximum face velocity through the
Configuration Tool.
2 analog outputs
0 VDC to 10 VDC, 4 mA to 20 mA
1 analog inputs
0 VDC to 10 VDC
Power supply
Class 2, 24 VAC ± 10%, 30 VA universal 120/240 VAC to 24 VAC,
60/50 Hz, step-down isolation transformer provided
Cable type
Belden 1325A
Communications
BACnet MS/TP network
Two-wire twisted pair, RS-485 signaling
Cable type
Belden 3107A
Touch screen user
interface
LCD size
3.2 in. diagonal
LCD type
Transmissive
Resolution
240 pixels x 320 pixels portrait
Viewing area
50.6 mm x 66.8 mm
Color depth
18-bit or 262K colors
Back light color
White
Luminous intensity
Min 2500 cd/m2
Mechanical
VMS-1655M surface-mount enclosure
(height x width x depth)
5 in. x 3 in. x 1.13 in.
External vortex sensor housing
(height x width x depth)
4 in. x 2.5 in. x 2 in.
Stainless steel cover plate for flow tube
(height x width x depth)
4.5 in. x 2.7 in. x 0.2 in.
VMS-1655M with flow tube cover plate
Approx. 3.5 lb
VMS-1655M with vortex sensor
Approx. 4.0 lb
Flow tube cover plate mounting
Flush
Environmental
Operating temperature
32°F to 125°F
Operating humidity
10% - 95%