MODULE SETTINGS
BACnet
®
Objects
HMS-1650
-
38
-
The following table itemizes the list of points available for integration in a building management system (BMS). This table contains the objects for
open BACnet integration.
Object Instance
Functional Description
Read or Write
Analog Inputs
AI - 1
Analog Input 1 (default: Fume Hood Face Velocity)
Read-Only
AI - 2
Analog Input 2 (default: Secondary Face Velocity)
Read-Only
AI - 3
Analog Input 3 (default: Sash Position Sensor)
Read-Only
AI - 4
Analog Input 4 (default: Exhaust Air Flow Volume)
Read-Only
AI - 5
Thermistor Input 1 (default: Ambient Temperature)
Read-Only
AI - 6
Thermistor Input 2 (default: Duct Temperature)
Read-Only
Analog Outputs
AO - 1
Analog Output 1 (default: Exhaust Damper Position)
Read-Only
AO - 2
Analog Output 2 (spare control output)
Read-Only
AO - 3
Analog Output 3 (spare control output)
Read-Only
AO - 4
Analog Output 4 (spare control output)
Read-Only
Binary Inputs
BI - 1
Digital Input 1 (default: Fume Hood Sash Switch)
Read-Only
BI - 2
Digital Input 2 (default: Secondary Sash Switch)
Read-Only
BI - 3
Digital Input 3 (spare digital input)
Read-Only
BI - 4
Digital Input 4 (spare digital input)
Read-Only
Binary Outputs
BO - 1
Relay Output 1 (default: Primary Alarm Relay Output)
Read-Only
BO - 2
Relay Output 2 (default: Secondary Alarm Relay Output)
Read-Only
BO - 3
Relay Output 3 (spare relay output)
Read-Only
BO - 4
Relay Output 4 (spare relay output)
Read-Only
Binary Values
BV-1
Occupancy Status
Read/Write
BV-2
Emergency Purge (MAX FLOW)
Read/Write
Analog Values
AV - 1
AI-1 Setpoint (Fume Hood Face Velocity Setpoint)
Read/Write
AV - 2
AI-2 Setpoint (Secondary Face Velocity Setpoint)
Read/Write
AV - 3
AI-3 Setpoint
Read/Write
AV - 4
AI-4 Setpoint
Read/Write
AV - 5
TI-1 Setpoint (Ambient Temperature Setpoint)
Read/Write
AV - 6
TI-2 Setpoint
Read/Write
AV - 7
Air Change Rate based on Flow Input at AI-1
Read/Write
AV - 8
Air Change Rate based on Flow Input at AI-2
Read/Write
AV - 9
Air Change Rate based on Flow Input at AI-3
Read/Write
AV - 10
Air Change Rate based on Flow Input at AI-4
Read/Write
AV - 11
Alarm Relay 1 High Setpoint
Read/Write
AV - 12
Alarm Relay 1 Low Setpoint
Read/Write
AV - 13
Alarm Relay 2 High Setpoint
Read/Write
AV - 14
Alarm Relay 2 Low Setpoint
Read/Write
AV - 15
Alarm Relay 3 High Setpoint
Read/Write
AV - 16
Alarm Relay 3 Low Setpoint
Read/Write
AV - 17
Alarm Relay 4 High Setpoint
Read/Write
AV - 18
Alarm Relay 4 Low Setpoint
Read/Write
AV - 19
AI-1 Low Alarm Setpoint (Low Face Velocity Alarm Setpoint)
Read/Write
AV - 20
AI-1 Low Warning Setpoint (Low Face Velocity Warning Setpoint)
Read/Write
AV - 21
AI-1 High Warning Setpoint (High Face Velocity Warning Setpoint)
Read/Write