MODULE SETTINGS
BACnet
®
Objects
HMS-1650
-
39
-
Object Instance
Functional Description
Read or Write
AV - 22
AI-1 High Alarm Setpoint (High Face Velocity Alarm Setpoint)
Read/Write
AV - 23
AI-2 Low Alarm Setpoint
Read/Write
AV - 24
AI-2 Low Warning Setpoint
Read/Write
AV - 25
AI-2 High Warning Setpoint
Read/Write
AV - 26
AI-2 High Alarm Setpoint
Read/Write
AV - 27
AI-3 Low Alarm Setpoint
Read/Write
AV - 28
AI-3 Low Warning Setpoint
Read/Write
AV - 29
AI-3 High Warning Setpoint
Read/Write
AV - 30
AI-3 High Alarm Setpoint
Read/Write
AV - 31
AI-4 Low Alarm Setpoint
Read/Write
AV - 32
AI-4 Low Warning Setpoint
Read/Write
AV - 33
AI-4 High Warning Setpoint
Read/Write
AV - 34
AI-4 High Alarm Setpoint
Read/Write
AV - 35
TI-1 Low Alarm Setpoint
Read/Write
AV - 36
TI-1 Low Warning Setpoint
Read/Write
AV - 37
TI-1 High Warning Setpoint
Read/Write
AV - 38
TI-1 High Alarm Setpoint
Read/Write
AV - 39
TI-2 Low Alarm Setpoint
Read/Write
AV - 40
TI-2 Low Warning Setpoint
Read/Write
AV - 41
TI-2 High Warning Setpoint
Read/Write
AV - 42
TI-2 High Alarm Setpoint
Read/Write
AV - 43
Writable Network Variable – Humidity
Read/Write
AV - 44
Writable Network Variable – Temperature
Read/Write
AV - 45
Writable Network Variable – Air Changes
Read/Write
AV - 46
Writable Network Variable – Differential Pressure
Read/Write
AV - 47
Device ID Offset (range: 0 – 4,194,000)
Read/Write
AV - 48
Duct Air Flow based on AI-1 flow input
Read-Only
AV - 49
Duct Air Flow based on AI-2 flow input
Read-Only
AV - 50
Duct Air Flow based on AI-3 flow input (Supply Flow)
Read-Only
AV - 51
Duct Air Flow based on AI-4 flow input (Exhaust Flow)
Read-Only
AV - 52
Volumetric Offset (Supply Flow – Exhaust Flow)
Read-Only
AV - 53
Volumetric Offset Setpoint
Read-Write
AV - 54
AO-1 Override Level
Read-Write
AV - 55
AO-2 Override Level
Read-Write
AV - 56
AO-3 Override Level
Read-Write
AV - 57
AO-4 Override Level
Read-Write
Multistate Objects
MSO - 1
Fume Hood Operating Mode: 1=occupied, 2=unoccupied, 3=standby
Read/Write
MSO - 2
Secondary Operating Mode: 1=occupied, 2=unoccupied, 3=standby
Read/Write
MSO - 3
Fume Hood Face Velocity Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
MSO - 4
Secondary Face Velocity Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
MSO - 5
AI-3 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
MSO - 6
AI-4 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
MSO - 7
TI-1 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only