MODULE SETTINGS
HMS-1650
-
37
-
Table 1. Analog Input Configuration Settings (S1)
Mode
S1 - 1
S1 - 2
S1 - 3
S1 - 4
S1 - 5
S1 - 6
S1 - 7
S1 - 8
AI-1 5Vdc
OFF
OFF
AI-1 20mA
ON
OFF
AI-1 10Vdc
OFF
ON
Not Valid
ON
ON
AI-2 5Vdc
OFF
OFF
AI-2 20mA
ON
OFF
AI-2 10Vdc
OFF
ON
Not Valid
ON
ON
AI-3 5Vdc
OFF
OFF
AI-3 20mA
ON
OFF
AI-3 10Vdc
OFF
ON
Not Valid
ON
ON
AI-4 5Vdc
OFF
OFF
AI-4 20mA
ON
OFF
AI-4 10Vdc
OFF
ON
Not Valid
ON
ON
Table 2. Protocol Selection Settings (S3)
Protocol Selection
S3-7
S3-8
Reserved
OFF
OFF
Metasys® N2
ON
OFF
LonWorks®
OFF
ON
BACnet® MS/TP (default)
ON
ON
Controller Configuration Dipswitch (S4)
1.
AO-1 Voltage Range Selection:
OFF = 0-10Vdc
ON = 0 - 5Vdc
2.
AO-2 Voltage Range Selection:
OFF = 0-10Vdc
ON = 0 - 5Vdc
3.
AO-3 Voltage Range Selection:
OFF = 0-10Vdc
ON = 0 - 5 Vdc
4.
AO-4 Voltage Range Selection:
OFF = 0-10Vdc
ON = 0 - 5 Vdc
Controller Configuration Slideswitch (S2)
Controller Configuration Slideswitch (S5):
LEFT = Analog Outputs powered by remote source
LEFT = Digital Inputs pulled-high (triggered by active low input -
default)
RIGHT = Analog Outputs powered locally by HMS1650 (default)
RIGHT = Digital Inputs pulled-low (triggered by active high input, up to
24Vdc)
Configurations & Settings