MOUNTING/WIRING
HMS-1650
-
23
-
Analog Input Dual Flow Sensors
NOTE: If using Honeywell sidewall sensor module,
the three terminals are +, IN, and G. The + terminal
should be connected to +10V; IN should be
connected to AI_1, and G should be connected to
AGND at the HMS-1650 backplane.
Triatek reserves the right to change product specifications without notice.
Triatek reserves the right to change product specifications without notice.
Controller Configuration Dipswitch Settings
S1 - 1 = OFF, S1 - 5 = OFF (AI - 1 set as 0 - 5V Input)
S1 - 2 = OFF, S1 - 6 = OFF (AI - 2 set as 0 - 5V Input)
NOTE: If using Honeywell sidewall sensor module,
the three terminals are +, IN, and G. The + terminal
should be connected to +10V; IN should be
connected to AI_1, and G should be connected to
AGND at the HMS-1650 backplane.