cascade Settings
36
only make adjustments to this setting after consulting Triangle Tube
Technical Support. Improper adjustment of cH Proportional Gain
could lead to temperature fluctuations and erratic cascade operation.
cH Integral Gain
default: 245
CH Integral Gain allows the cascade response to be adjusted for a central
heating call. CH Integral Gain has the greatest influence when the system
temperature is close to the setpoint. Press the
LEfT
or
RIGHT
buttons to
adjust the CH Integral Gain then press the
oK
button to store the setting.
•
Increase cH Integral Gain
-
The Cascade System will take longer to reach the setpoint, but
setpoint overshooting is minimized.
-
If the setpoint is reached too quickly, increase the CH Integral
Gain value by 2. Perform Cascade Autodetection and initiate a
central heating call. Observe the cascade response and make fur-
ther adjustments if necessary.
•
decrease cH Integral Gain
-
The Cascade System will reach setpoint faster, but overshooting
the setpoint may occur.
-
To reach the setpoint faster, decrease the CH Integral Gain value
by 2. Perform Cascade Autodetection and initiate a central heat-
ing call. Observe the cascade response and make further adjust-
ments if necessary.
only make adjustments to this setting after consulting Triangle Tube
Technical Support. Improper adjustment of cH Integral Gain could
lead to temperature fluctuations and erratic cascade operation.
dHW Proportional Gain
default: 10
DHW Proportional Gain allows the cascade response to be adjusted for a
domestic hot water call. DHW Proportional Gain has the greatest influ-
ence when the system temperature is far away from the setpoint. Press the
LEfT
or
RIGHT
buttons to adjust the DHW Proportional Gain then press
the
oK
button to store the setting.
•
Increase dHW Proportional Gain
-
The Cascade System will reach setpoint faster, but overshooting
the setpoint may occur.
NOTICE
NOTICE
1
255
10
DHW Proportional Gain
1
255
245
CH Integral Gain
Содержание Prestige Excellence
Страница 13: ...11 cH Settings fig 2 System Piping with System Pump cH1 cH2 dHW...
Страница 14: ...12 cH Settings fig 3 System Piping with System Pump cH1 cH2...
Страница 15: ...13 fig 4 System Piping with System Pump cH2 cH Settings...
Страница 33: ...31 cascade Installation fig 11 Split cascade Wiring note Reference Fig 10 page 30 for cascade piping...