15
demand Type
PRESTIGE Solo default: Switch
PRESTIGE Excellence default: Sensor
Demand Type allows the installer to select the type of device which will
generate a domestic hot water call. Press the
UP
or
doWn
buttons to
select the DHW Demand Type then press the
oK
button to store the set-
ting. The DHW Demand options are:
•
Switch
- A domestic hot water call from an aquastat or dry contact
switch will enable the Prestige with a fixed setpoint for a domestic
hot water call.
•
Sensor
- This option requires the use of Indirect Water Heater Sensor
PSRKIT22 which is included with every PRESTIGE Solo. The
PRESTIGE Excellence utilizes an Indirect Water Heater Sensor. The
Prestige will monitor the DHW storage temperature and generate a
domestic hot water call when the temperature drops below the DHW
Storage Setpoint - DHW On Differential.
Boiler dHW Setpoint
default: 186ºf [86ºc]
Boiler DHW Setpoint is the fixed boiler setpoint temperature during a
domestic hot water call when the Switch option is chosen in DHW
Demand. Press the
LEfT
or
RIGHT
buttons to adjust the Boiler DHW
Setpoint then press the
oK
button to store the setting.
dHW Storage Setpoint
default: 140°f [60°c]
DHW Storage Setpoint is the domestic hot water storage setpoint temper-
ature when the Sensor option is chosen in DHW Demand. Press the
LEfT
or
RIGHT
buttons to adjust the DHW Storage Setpoint then press the
oK
button to store the setting.
The boiler setpoint is automatically set to the dHW Storage
Se dHW Storage adder when the Sensor option is cho-
sen in dHW demand.
dHW on differential
default: 6°f [3°c]
DHW On Differential sets how far the DHW storage temperature must fall
below the DHW Storage Setpoint to create a domestic hot water call when
the Sensor option is chosen in DHW Demand. The domestic hot water call
will end when the DHW storage temperature rises above the DHW
Storage Setpoint. Press the
LEfT
or
RIGHT
buttons to adjust the DHW
On Differential then press the
oK
button to store the setting.
NOTICE
dHW Settings
96ºF
194ºF
186ºF
Boiler
DHW Setpoint
4ºF
18ºF
6ºF
DHW On Differential
68ºF
150ºF
140ºF
DHW
Storage Setpoint
Demand Type
Switch
Sensor
Switch
Содержание Prestige Excellence
Страница 13: ...11 cH Settings fig 2 System Piping with System Pump cH1 cH2 dHW...
Страница 14: ...12 cH Settings fig 3 System Piping with System Pump cH1 cH2...
Страница 15: ...13 fig 4 System Piping with System Pump cH2 cH Settings...
Страница 33: ...31 cascade Installation fig 11 Split cascade Wiring note Reference Fig 10 page 30 for cascade piping...