factory Trimax Settings
20
domestic Setting
factory default
Minimum Setting
Minimum Setting
EZ Setup Reset Installer Reset
dHW operation
Enabled
Prestige Model
Solo
demand
Switch
Boiler dHW Setpoint
186°f [86°c]
96°f [35°c]
194°f [90°c]
dHW Storage Setpoint
140°f [60°c]
68°f [20°c]
150°f [65°c]
dHW on differential
6°f [3°c]
4°f [2°c]
18°f [10°c]
dHW Storage adder
46°f [25°c]
0°f [0°c]
54°f [30°c]
dHW Post Pump Time
1 minute
off
30 minutes
dHW Priority Timeout
off
off
60 minutes
dHW Priority
Enabled
dHW call Blocking
0 minute
0 minute
30 minutes
dHW to cH call Blocking
1 minute
0 minute
30 minutes
antilegionella function
disabled
Heating Setting
factory default
Minimum Setting
Maximum Setting
EZ Setup Reset Installer Reset
Heating operation
Enabled
demand
Switch & Setpoint
absolute Max cH Setpoint
194°f [90°c]
68°f [20°c]
194°f [90°c]
cH1 Maximum Setpoint
180°f [82°c]
68°f [20°c]
194°f [90°c]
cH1 Minimum Setpoint
120°f [49°c]
60°f [15°c]
140°f [60°c]
Reset curve coldest day
0°f [-18°c]
-30°f [-34°c]
50°f [10°c]
Reset curve Warmest day
64°f [18°c]
60°f [15°c]
78°f [25°c]
cH2 circuit
Enabled
cH2 Maximum Setpoint
140°f [60°c]
68°f [20°c]
194°f [90°c]
cH2 Minimum Setpoint
80°f [27°c]
60°f [15°c]
140°f [60°c]
Warm Weather Shutdown
off
off
78°f [25°c]
Pump constant circulation
disabled
cH Post Pump Time
1 minute
off
20 minute
freeze Protection
Enabled
frost Protection Setpoint
-22°f [-30°c]
-22°f [-30°c]
50°f [10°c]
Parallel Shift Value
0°f [0°c]
0°f [10°c]
144°f [80°c]
cH call Blocking
1 minute
0 minute
30 minutes
System Pump
cH1/cH2
cascade Setting
factory default
Minimum Setting
Maximum Setting
EZ Setup Reset Installer Reset
Stage delay
60 seconds
0 second
255 seconds
Minimum firing Rate
30%
0%
100%
Maximum firing Rate
398 MBH [117kW]
0 MBH [0kW]
869 MBH [255kW]
cH or dHW Boilers
0
0
6
cH Proportional Gain
10
1
255
cH Integral Gain
245
1
255
dHW Proportional Gain
10
1
255
dHW Integral Gain
245
1
255
Modbus address
0=BcST
0
247
factory Trimax Settings
Содержание Prestige Excellence
Страница 13: ...11 cH Settings fig 2 System Piping with System Pump cH1 cH2 dHW...
Страница 14: ...12 cH Settings fig 3 System Piping with System Pump cH1 cH2...
Страница 15: ...13 fig 4 System Piping with System Pump cH2 cH Settings...
Страница 33: ...31 cascade Installation fig 11 Split cascade Wiring note Reference Fig 10 page 30 for cascade piping...