cascade Settings
33
navigation: Home Screen>Installer Menu>cascade>cascade
Settings
The Cascade Settings menu contains settings related to cascade operation.
Each line contains a Cascade Setting followed by its current value. Six
Cascade Settings are displayed on the screen at one time. Press the
UP
or
doWn
buttons to scroll through additional Cascade Settings.
cascade Setting changes must be made on the cascade Master.
cascade autodetection must be performed after making any
changes to a cascade Setting before the change will take effect.
Stage delay
default: 60 Seconds
Stage Delay sets the time delay before enabling or disabling a boiler in the
Cascade System
. The Stage Delay begins once the Master boiler determines that
a boiler must be enabled to reach the setpoint or when the Master boiler deter-
mines a boiler should be disabled because of a decreasing load. Press the
LEfT
or
RIGHT
buttons to adjust the Stage Delay then press the
oK
button to store
the setting. Adjusting the Stage Delay will have the following effects:
•
Increase Stage delay
-
Reaching the setpoint could take longer due to a longer delay
between enabling boilers.
-
Overshooting the setpoint could occur due to boilers staying on
longer before being disabled.
•
decrease Stage delay
-
Overshooting the setpoint could occur due to boilers being
enabled quicker.
-
Boilers will be disabled quicker, possibly increasing boiler
cycling and decreasing runtimes.
Minimum firing Rate
default: 30%
Minimum Firing Rate is the minimum firing rate of a single boiler in the Cascade
System. The Master boiler uses this setting to determine when boilers can be
enabled and disabled. Setting the Minimum Firing Rate below the recommend-
ed minimum will result in boilers being enabled too quickly which may cause
sharp increases in temperature from the Cascade System. Setting the Minimum
Firing Rate above the recommended minimum will delay the enabling of boilers
which may lower the system efficiency. Press the
LEfT
or
RIGHT
buttons to
adjust the Minimum Firing Rate then press the
oK
button to store the setting.
The minimum recommended settings are:
NOTICE
cascade Settings
Prestige Model
Minimum Firing Rate
Solo 60
28%
Solo 110 Natural Gas
29%
Solo 110 Propane Gas
27%
Solo 175
31%
Solo 250
28%
Solo 399
30%
Cascade Setting
Stage Delay
Minimum Firing Rate
Maximum Firing Rate
CH or DHW Boilers
CH Proportional Gain
CH Integral Gain
60 sec
30%
398 MBH
0
10
245
Stage Delay
60 sec
0%
100%
30%
Minimum Firing Rate
0sec.
255sec.
60Sec.
Stage Delay
Содержание Prestige Excellence
Страница 13: ...11 cH Settings fig 2 System Piping with System Pump cH1 cH2 dHW...
Страница 14: ...12 cH Settings fig 3 System Piping with System Pump cH1 cH2...
Страница 15: ...13 fig 4 System Piping with System Pump cH2 cH Settings...
Страница 33: ...31 cascade Installation fig 11 Split cascade Wiring note Reference Fig 10 page 30 for cascade piping...