12
CHAPTER
3
CHAPTER 3 - WATER HEATER START-UP
3.5. DHW Frost Protection
The Indirect Water Heater (IDWH) Sensor used in the
Prestige Excellence provides a Frost Protection feature
to the water heater. The Frost Protection feature is de-
signed to protect the Excellence water heater from
a potential freeze up. Frost Protection will generate
a DHW call once the IDWH temperature falls below
42º F [6ºC]. Once Frost Protection is activated, the inter-
nal circulator and diverter valve will direct water flow
to the water heater and the burner will fire. Frost Pro-
tection will end once the IDWH temperature is raised
to 60ºF [16ºC]. This feature is always active and cannot
be disabled. Frost Protection is still active even if DHW
operation has been disabled.
3.6. CTRLMax Factory Settings
DHW SETTING
FACTORY
DEFAULT
MINIMUM
SETTING
MAXIMUM
SETTING
EZ SETUP RESET
INSTALLER RESET
DHW Operation
Enabled
3
Demand Type
Sensor
DHW Boiler Setpoint
168°F [75°C]
96°F [35°C]
188°F [87°C]
3
3
DHW Setpoint
140°F [60°C]
68°F [20°C]
168°F [75°C]
3
3
DHW On Differential
6°F [3°C]
4°F [2°C]
18°F [10°C]
3
DHW Storage Adder
28°F [15°C]
10°F [5°C]
54°F [30°C]
3
DHW Post pump time
2 Minutes
Off
30 minutes
3
DHW Priority Timeout
Off
Off
120 Minutes
3
3
DHW Priority
Enabled
3
DHW Call Blocking
1 Minute
0 Minute
30 Minutes
3
DHW to CH Call Blocking
0 Minute
0 Minute
30 Minutes
3
Antilegionella Function
Enabled
Enabled
Disabled