CHAPTER 2 - DOMESTIC PIPING

2.5.2  Commonwealth of Massachusetts Instal-

lation

•  Thread a 3/4” close nipple onto the Auxiliary 

connection and insert an open-end dip tube 

into the Auxiliary connection on top of water 
heater. As shown in 

 Fig. 2 on page 4

.

•  Install a 3/4” NPT elbow on the Auxiliary con-

nection.

•  Pipe the  drain valve piping from the elbow 

connection to:

 

Ū

a suitable place for disposal

 or

 

Ū

terminate within 12” of the floor.

2.6.  Manual Air Vent 

•  A manual air vent is factory installed.
•  Open manual air vent and once the tank is full 

and air has stopped escaping, close the manual 

air vent. 

2.7.  Thermal Expansion

If a backflow preventer, check valve or pressure reduc-

ing valve is piped on cold water supply piping of water 

heater, install an expansion tank on cold water supply 

line to prevent thermal expansion from repeatedly forc-

ing open T&P relief valve.

T&P relief valve is not intended for constant 

duty, such as relief of pressure due to repeated 

normal thermal expansion.  Correct this con-

dition by installing a properly sized expansion 

tank in the domestic water system.  Refer to 

expansion tank manufacturer’s installation in-

structions for proper sizing.

2.8.  Water Hammer

Dishwashers, clothes washers and fast-closing positive 

shut-off valves incorporated in the system all contrib-

ute to creating water shock.  Install a water hammer ar-

rester to prevent damage to pipes and appliances.  See 

device manufacturer’s instructions for application and 

installation.

NOTICE

Water hammering within the domestic piping 

system can cause premature failure of the inner 

tank of the water heater. This type of failure is 

NOT covered under warranty. 

2.9.  Vacuum Breaker

Installing a vacuum breaker on the domestic cold water 

inlet will prevent damage to the inner tank if a negative 

pressure is developed in the domestic supply line.  See 

manufacturer’s instructions for application and installa-

tion of the vacuum breaker.

2.10.  General Piping

•  For domestic water piping diagrams, see

 Fig. 4 

 and 

 

Fig. 5 on page 7, and Fig. 6 on page 8. 

•  All plumbing must meet or exceed all local, state 

and national plumbing codes.

•  Use pipe dope or tape suitable for potable water 

systems.

•  Use isolation valves to isolate system components.

2.11.  Domestic Piping

•  Union on domestic hot water outlet should be 

piped at a higher elevation than domestic water 

drain valve.  This will make draining the water heat-

er easier.

•  Use dielectric unions or couplings to protect hot 

and cold water fittings from corrosion when con-

necting dissimilar materials such as copper and gal-

vanized iron pipe.

•  If copper pipe is used for domestic water connec-

tions, first solder pipe to a threaded adapter and 

then screw adapter into cold water inlet on top of 

Excellence.  Cold Water Inlet contains an internal 

plastic dip tube which can be damaged by heat 

from soldering.

 

Do not apply heat to the cold water in-

let when making sweat connections to water 

heater.  Sweat tubing to adapter before fitting 

adapter to cold water inlet of heater.  It is imper-

ative that no heat be applied to the cold water 

inlet, as it contains a non metallic dip tube.

NOTICE

NOTICE

Содержание PRESTIGE Excellence 110

Страница 1: ...e or shortage in shipment must be filed immediately against the transportation company by the consignee Leave all documentation received with appliance with the owner for future reference NOTICE WARNI...

Страница 2: ...INTENTIONALLY LEFT BLANK...

Страница 3: ...P Relief Valve Discharge Piping 4 2 5 Domestic Drain Valve 4 2 5 1 Standard Installation 4 2 5 2 Commonwealth of Massachusetts Installation 5 2 6 Manual Air Vent 5 2 7 Thermal Expansion 5 2 8 Water Ha...

Страница 4: ...e by qualified service technician 13 4 1 2 Homeowner monthly maintenance 13 4 2 Filling Water Heater 13 4 3 Draining Water Heater 13 4 4 Draining Outer Boiler Water Tank 14 4 5 Draining Inner Domestic...

Страница 5: ...nstallation Domestic Piping Excellence Series 7 Fig 5 Domestic Piping with Optional Recirculation Excellence Series 7 Fig 6 Standard Installation Domestic Piping with Optional Storage Tank 8 Fig 7 PRE...

Страница 6: ...INTENTIONALLY LEFT BLANK...

Страница 7: ...recommendations made by Triangle Tube for the installers which will help to ensure optimum operation and longevity of the equip ment DANGER WARNING CAUTION NOTICE BEST PRACTICE BEST PRACTICE IMPORTAN...

Страница 8: ...features of its products without prior notice Check for an updated version of this manual at www triangletube com NOTICE viii SAFETY PRODUCT AND SAFETY INFORMATION Protection must be taken against exc...

Страница 9: ...wing requirements The heat transfer medium is potable water or contains only substances which are recognized as safe by the U S Food and Drug Administration The pressure of the heat transfer medium is...

Страница 10: ...NOTICE CHAPTER 1 PRE INSTALLATION REQUIREMENTS If the recommended clearances listed above cannot be maintained or the enclo sure in which the boiler is installed is less than 85 cubic feet the space...

Страница 11: ...omply with this instruction can re sult in minor property damage or injury CAUTION The PRESTIGE Excellence water heater must be protect ed with a T P relief valve Size the Excellence T P relief valve...

Страница 12: ...of piping can reduce discharge capacity Directly connected to a drain Terminate dis charge piping within 6 from drain Refer to lo cal codes Plugged reduced or restricted Subject to freezing Do not ins...

Страница 13: ...tion and installation NOTICE Water hammering within the domestic piping system can cause premature failure of the inner tank of the water heater This type of failure is NOT covered under warranty 2 9...

Страница 14: ...revent potential scald ing hazards the recirculation loop should be controlled by an aquastat DO NOT use con tinuous recirculation Failure to comply with this instruction will re sult in serious injur...

Страница 15: ...ith Optional Recirculation Excellence Series 1 Shut off valve 2 Flow check valve 3 Mixing valve with check valve 4 Vacuum Breaker 5 Unions 6 Backflow preventer or pressure reducing valve 7 Circulator...

Страница 16: ...al Storage Tank 1 Shut off valve 2 Flow check valve 3 Mixing valve with check valve 4 Vacuum Breaker 5 Unions 6 Backflow preventer or pressure reducing valve 7 Circulator controlled by aquastat 8 Dome...

Страница 17: ...filled and pressurized before pressurizing outer tank Failure to comply with these instructions can result in minor property damage or injury Reference the PRESTIGE Excellence boiler man ual for boile...

Страница 18: ...odes require certain water tempera tures at hot water faucets take special precautions Install the factory supplied automat ic mixing valve at water heater and or install a point of use mixing valve a...

Страница 19: ...e DHW PriorityTimeout screen then appears see below Default 168 F 75 C The Prestige Excellence utilizes an Indirect Water Heater Sensor When Sensor is selected in Select DHW Demand use of an Indirect...

Страница 20: ...ature is raised to 60 F 16 C This feature is always active and cannot be disabled Frost Protection is still active even if DHW operation has been disabled 3 6 CTRLMax Factory Settings DHW SETTING FACT...

Страница 21: ...r heater resulting in substantial property damage serious injury or death Follow instructions on circulator to oil it if required Check mixing valve valves pipes and fittings for leaks Check function...

Страница 22: ...WARNING 4 4 Draining Outer Boiler Water Tank 1 Disconnect power supply to water heater 2 Close boiler isolation valves 3 Connect hose to boiler water drain valve under wa ter heater Open and drain wat...

Страница 23: ...placement part Use only genuine Triangle Tube replacement parts to ensure warranty coverage and to avoid improper operation or damage to appliance ContactTriangleTube at 856 228 8881 or www triangletu...

Страница 24: ...INTENTIONALLY LEFT BLANK...

Страница 25: ...C D E F G H Connection 3 4 NPSC Pres sure Relief Valve 3 Vent Outlet 3 Combustion Air Inlet 1 NPT Boiler Return 1 2 NPT Gas Connection 1 NPT Boiler Supply Boiler Width Boiler Height Dimension in mm 2...

Страница 26: ...R SPECIFICATIONS Fig 9 Right Side View PRESTIGE Excellence 110 I J K L Connection 3 Combustion Air Inlet 3 Vent Outlet Boiler Drain 1 NPT Boiler Return Supply Boiler Depth Dimension in mm 4 3 4 120 9...

Страница 27: ...D E Connection 3 4 NPSC Aux Connection rear 3 4 DHW inlet and outlet 3 4 DHW Inlet 3 4 NPSC Aux Connection rear Manual Air Vent 3 4 DHW outlet Dimension in mm 6 151 11 1 2 292 4 3 4 121 7 5 8 191 10 3...

Страница 28: ...20 CHAPTER 6 CHAPTER 6 WATER HEATER SPECIFICATIONS 6 1 Performance...

Страница 29: ...21...

Страница 30: ...22...

Страница 31: ...23...

Страница 32: ...eat Exchangers Constructed of high quality corrosion resistant stainless steel AISI 316 or titanium Specially designed built in flow restrictor to assure maximum heat exchange Compact and light weight...

Отзывы: