FAULT FINDING (Cont’d)
FAULT
POSSIBLE CAUSE
ACTION
POOR FLAME CUT-OFF
Air in pump or at back of nozzle
Bleed pump through pressure gauge port,
also check for leaks in oil line if 2-pipe
system.
Oil contaminated with water
Run off oil at burner until free of water and
drain condensation from tank.
Dirt in solenoid valve
Clean or replace valve.
Pump shut-off piston sticking
Replace pump.
MORNING START LOCK-OUT
Faulty non-return valve or air leak
Replace non-return valve and cure leak.
in two pipe system
Low voltage
Check with local Electricity Board.
Combustion readings incorrect
Check combustion under normal running
conditions and compare readings with
those given under ‘Burner Settings’.
Oil level in tank falling below burner
Raise tank or fit a 2-pipe system.
COMBUSTION FUMES
Door not secure
Tighten wing nuts, securing door in
SMELL
position
Seals on cleaning covers
Change door seals
Burner incorrectly fitted
Check burner gaskets and replace if
damaged, tighten burner fixing nuts
Flue Gasket
Check flue is correctly sealed to boiler
flue outlet.