Servicing the Boiler
1 Remove the flexible air supply hose from the flue kit
to the burner.
2 Remove burner ensure that if flexible oil supply hose
has to be disconnected that there is no spillage of oil.
3 Remove both flue-cleaning covers from front of boiler
lift out flue baffles from boiler then slide baffles out of
condensing unit.
4 Brush all deposits from the flue baffles and clean the
internal surfaces of the boiler.
5 Remove any flue deposits from the combustion chamber
floor using a vacuum cleaner.
6 Clean the flue way surfaces of the condenser unit
removing any deposits.
7 Check flue sealing gasket.
8 Inspect flue cleaning door seals and replace if necessary.
FIG. 20 BAFFLE DETAILS FOR TRIANCO PREMIER 50/90
BAFFLES
CONDENSING UNIT
FLUE COVER
FLUE GAS SAMPLE
POINTS
IMPORTANT
WHEN RE-FITTING BAFFLES ENSURE THEY
ARE RE-FITTED AS SHOWN IN ARRANGEMENT
SHOWN IE GAP ALTERNATING FROM FRONT TO
BACK ON BOILER BAFFLES.
BOILER FLUE
COVER
PART NO 223053
1-OFF
PART NO
223050
4-OFF
PART NO
223076
2-OFF
9 Check to ensure that the condense drain is working
and not blocked by pouring a small amount of water
into condenser unit and checking to see that water
discharges from condense port.
10 Replace flue baffles in correct arrangement (see diagram)
Refit both flue covers securing in position making gas
tight seal using washers and wing nuts previously removed.
11 Check condensate trap to ensure the outlet is not
obstructed.
12 Refit the burner securing the air hose in position using
the clips provided.
13 Reconnect the flexible oil line to the burner (if removed).
14 Turn on oil supply, switch on electricity ensure system
is calling for heat, boiler should now fire.
15 Finally check the combustion settings to those given
under Burner Settings and make any adjustments
where necessary.