7. COMMISSIONING

The boiler/burner 

MUST

be commissioned by a qualified

technician, OFTEC trained and registered.

It is the responsibility of the installer to ensure the boiler
is properly commissioned, failure to do so will make the
boiler’s guarantee and any extended warranty null and
void.

Although all burners are factory tested before despatch,
they will usually need further air adjustment to achieve
the readings indicated in ‘Burner detail leaflet’ because of
site variations in flue draught and back pressure.

Procedure

1.

Switch off electrical supply to the boiler.

2.

Ensure boiler is full of water and all valves are open.

3.

Remove flue-cover and check that flue-baffles are
correctly positioned (See Fig 20 for baffle 
arrangement).

4.

Disconnect oil hose from burner, open shut-off valve
and run off a quantity of oil into a container to check
for a clean air free supply then reconnect hose.  (This
applies to single pipe gravity system only).

5.

Check that the time-switch (if fitted) is in the ON 
position and room and boiler thermostats are calling
for heat.

6.

Switch on electrical supply and the burner should
start.

Note: 

The burner may lock-out on first firing due to

air in the pump, if this happens, wait about a minute
before pressing reset button to restart burner.  If a
further lock-out occurs, the air should be bled from
the pump pressure gauge connection.

7.  Start and stop the burner two or three times until

the flame cuts off sharply - this indicates any 
remaining air has been dispersed.

8.

Allow the burner to run for about 15 minutes, then
take a CO

2

reading through the sampling hole in

flue-cover. Compare the reading with that given
under ‘Burner Settings’ and adjust the air setting if
necessary to achieve the required CO

2

%. Also,

check the smoke and flue gas temperature.

9.

If the system is not going to be put into immediate
operation, the fuel supply and electricity supply
should be isolated.
If there is a possibility that the boiler will not be running
during freezing conditions, the system should be     
drained down.

Handing Over

After completing the boiler installation, the installer
should make a thorough check of the system to ensure it
is completely satisfactory and demonstrate to the user
the operation of the boiler and any system controls.

All instructions should be handed to the user for retention
and advice regarding the need for annual servicing.

8. SERVICING

IMPORTANT: ISOLATE ELECTRICAL SUPPLY TO THE
BOILER BEFORE SERVICING

To maintain the boiler’s high thermal efficiency and
reliable operation, it should be serviced annually by a
qualified and registered OFTEC engineer.  Electrical work
should be carried out by a qualified engineer.

If the boiler is used to provide central heating and hot
water all year round, the best time for its annual service
is just before the start of the heating season.

Where the boiler is shut down for the summer months,
the service should be carried out as soon as possible
after the end of the heating season.

Oil tank

Open tank drain-cock to draw off any accumulated water
and sludge.

Line filters

Turn off oil supply and remove filter bowl.  Wash filter ele-
ment clean with kerosene.

Important
Before commencing with service work on either the
boiler or the fuel supply please read the health and
safety information.

Before servicing the boiler carry out the following checks.

1.  Ensure the air inlets on the flue terminal are not

blocked or obstructed.

2.  Check to ensure external controls are working correctly.

3.  Check ventilation openings are not obstructed and

are adequate for the size of the boiler.

4.  Inspect all connections to boiler to ensure they are

sound, remake any joints that are showing signs of
leakage.

5.  Inspect flexible oil supply lines and replace where

necessary.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание EuroStar Premier 50/90 Condensing

Страница 1: ...To be retained by householder USER INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS OIL FIRED CENTRAL HEATING BOILERS FOR BALANCED OR CONVENTIONAL FLUE BED 92 42 EEC EMC 89 336 EEC Premier 50 90 Con...

Страница 2: ...disposable gloves face masks and eye protection After handling wash hands and other exposed parts When disposing reduce dust with water spray ensure parts are securely wrapped GLUES SEALANTS PAINT Glu...

Страница 3: ...ilation 8 9 Extractor fan 9 Electrical supply 9 Condensate Drain Connection 10 5 OIL SUPPLY Oil storage tank Steel and Plastic 11 Oil supply line 11 Single pipe oil supply 12 13 Two pipe oil supply 12...

Страница 4: ...YOUR TRIANCO BOILER The Trianco EuroStar Condensing boiler has been designed and constructed to give years of trouble free service These instructions are provided to assist you in obtaining the best...

Страница 5: ...nk is topped up at regular intervals do not wait until the tank is nearly empty before refilling otherwise sludge and water could be sucked into the oil pipe to affect the burner s operation and reduc...

Страница 6: ...tallation and servicing instructions or The breakdown occurs immediately following an annual service visit In this instance your appointed Service Agent must check all his work PRIOR to requesting Tri...

Страница 7: ...by using a Trianco balanced flue kit These kits allow the boiler to be installed in a wide variety of site conditions see bal anced flue kit details Note Only circular low level horizontal balanced fl...

Страница 8: ...ENTRY BOTH SIDES RETURN CONNECTION DIA 22MM EACH SIDE FLOW CONNECTION DIA 22MM EACH SIDE Heating Return Cleaning Hole Heating Return Heating Flow Condensate drain Heating Flow Tee Elbow Condensate dra...

Страница 9: ...5 12 5 Burner See Burner Details Weight empty kg 140 Water content litre 26 Flow return connections 22 mm compression Flue Socket Dia C F in 4 Max operating pressure bar 3 psi 43 5 Test Pressure bar...

Страница 10: ...FIG 5 WIRING DIAGRAM 7...

Страница 11: ...ales Part F Section 111 Scotland Part L The Control of Pollution Oil Regulations Current I E E Regulations Local Water Undertakings By laws OFTEC Installation Requirements for Oil Fired Boilers and Oi...

Страница 12: ...h or low voltage fluctuations the oil burner shall be prevented from starting by the use of a voltage sensitive device if the voltage drops or increases sufficiently to endanger the installation Therm...

Страница 13: ...visible position and where no damage can be caused to the appliance or surroundings if the trap was to overflow When installing the condensate trap it is important that the trap is filled with water t...

Страница 14: ...re easier to handle because of their lower weight d They have a 10 year manufacturer s guarantee Plastic tanks should be fitted with similar components to those used with steel tanks Fire Protection T...

Страница 15: ...bar other wise dissolved gas will be released from the oil to affect combustion 2 The return pipe must end at the same level as the suction outlet to prevent loss of prime 3 The outlet from the tank...

Страница 16: ...ID 10 21 31 41 52 62 73 83 PIPE 8mm ID 33 66 98 100 100 100 100 100 MAXIMUM OIL SUPPLY LINE LENGTH L MAXIMUM LENGTH METRES LIFT H METRES 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 PIPE 6mm ID 48 42 36 30 24 18 1...

Страница 17: ...14 FIG 13 DE AERATED OIL SUPPLY INSTALLATION REFER TO MANUFACTURERS INSTRUCTIONS FOR OIL DE AERATOR INSTALLATION DETAILS REMOTE OPERATED FIRE VALVE OIL FILTER...

Страница 18: ...to run back in to the boiler No separate drain at the base of the flue system is required 3 Where an existing chimney is to be used it must be lined with a stainless steel liner that is approved for...

Страница 19: ...seal Trianco boilers have a sealed air duct system which maintains the room sealed performance even when the casing door is removed for burner commissioning or adjustments The use of the balanced flu...

Страница 20: ...aving the flue gasket in position 6 If the flue is to be fitted terminating to the left or right hand side of the boiler the corresponding section of side casing must be removed 7 To remove the sectio...

Страница 21: ...SEALING PLATE 1 8 GASKET SUPPLIED WITH BOILER 9 FLUE PIPE O RING 1 10 JUBILEE CLIP 1 230mm ROUND KIT 2334 2335 Supplied with boiler Supplied with boiler IMPORTANT When installing the flue system it is...

Страница 22: ...the flue system it is important that the flue assembly inclines slightly from the boiler This will allow any condensation formed in the flue to run back to the condense drain 2351 1000mm Horizontal Ro...

Страница 23: ...temperature 9 If the system is not going to be put into immediate operation the fuel supply and electricity supply should be isolated If there is a possibility that the boiler will not be running duri...

Страница 24: ...RE FITTING BAFFLES ENSURE THEY ARE RE FITTED AS SHOWN IN ARRANGEMENT SHOWN IE GAP ALTERNATING FROM FRONT TO BACK ON BOILER BAFFLES BOILER FLUE COVER PART NO 223053 1 OFF PART NO 223050 4 OFF PART NO...

Страница 25: ...ell not seeing flame Clean photo cell and ensure it is fully plugged in Air trapped in pump Bleed off air through pressure gauge tapping Solenoid valve faulty Check coil for continuity and replace if...

Страница 26: ...alve or air leak Replace non return valve and cure leak in two pipe system Low voltage Check with local Electricity Board Combustion readings incorrect Check combustion under normal running conditions...

Страница 27: ...e W U Boiler See Fig 20 4 12 Flue Cover Assembly boiler 1 223019 13 Control Box Assembly 1 221944 14 Control Panel 3 223097 15 Front Door Assembly 1 223083 16 Burner Assembly 1 223120 17 Hose 1 209491...

Страница 28: ...opyright in this brochure and the drawings or illustrations contained in it is vested in Trianco Limited and neither the brochure or any part thereof may be reproduced without prior written consent Tr...