Fireplace Insert Installation
(for qualified installers only)
9
© Travis Industries
100-01259
4150520
Insert Placement Requirements
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" (915mm) of the front of the insert (Figure 3 “q”).
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in Figure 3 must be met. Follow the
clearances for the type of fireplace being used – (masonry or zero-clearance-metal).
Side
Wall
Combustible Mantel
Combustible Top Facing
Non-Combustible
Hearth
Facing
q
l
k
p
x
o
n
m
Minimum
Clearances
Masonry
Fireplace
Z.C. (Metal)
Fireplace
k Sidewall
9"
229mm
9"
229mm
l Side Facing
(non-
combustible)
9"
229mm
9"
229mm
m Top Facing
(non-
combustible)
39"
991mm
39"
991mm
n Mantel
(combustible)
41.5"
1055mm
41.5"
1055mm
o Front Hearth
(does not
include insert
extension “x”)
16"
407mm (US)
- - - - - - - - - - -
18”
458mm
(Canada)
16"
407mm (US)
- - - - - - - - - - -
18”
458mm
(Canada)
p Side Hearth
8"
204mm
8"
204mm
q Front of Insert
36"
915mm
36"
915mm
x Extension Onto
Hearth
0"
0mm
0"
0mm
Figure 3
Hearth Requirements
Must extend 16" (USA) or 18” (Canada) in front of the insert and 8" on both sides.
Must be non-combustible and at least .018" thick (26 gauge)
Masonry Fireplace Requirements
Chimney must have a clay tile liner or a stainless steel liner (positive connection).
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert.
Chimney height: 15' (4.5M) minimum; 33' (10M) maximum (measured from base of insert).
Entire fireplace, including chimney, must meet local building requirements.
The fireplace insert must be placed on a masonry hearth built to UBC standards.