Installation
(for qualified installers only)
© Travis Industries
4100519
100-01197_001
Non-Combustible Facing
•
Non-combustible facing on the front of the fireplace must extend a minimum 12” from the top
of the glass frame. Above 12” combustibles may be used, but may not protrude more than 3/4”
from the non-combustible facing. Any combustible that protrudes more than 3/4” is considered
a mantel and must meet mantel clearances.
•
Non-combustible facing on the front of the fireplace must extend a minimum 6” to each side of
the glass frame. Beyond 6” combustibles may be used, but may not protrude more than 3/4”
from the non-combustible facing. Any combustible that protrudes more than 3/4” is considered
a side wall and must maintain the 10-1/4” side wall clearances.
•
The maximum depth for non-combustible facing is 6” (includes the fiber board).
Combustible Material