XT300C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

11

69-1212—1

Pub. No. 18-HD25D1-3

TROUBLESHOOTING (

C

ONTINUED

).

Symptom

Possible Cause

Action

Heating will not come
on.

No power to the thermostat.

Check for 24 Vac between R and W terminals.

If missing 24 Vac:
Check if the circuit breaker is tripped—reset the circuit breaker.
Check if the system fuse is blown—replace the fuse.
Check if the power switch on the HVAC equipment is in the  
Off position—set to the On position.
Check wiring between thermostat and HVAC equipment—replace
any broken wires and tighten any loose connections.
If 24 Vac is present, proceed with troubleshooting.

Heating will not come
on.

Thermostat minimum off time is
activated.

Wait up to five minutes for the system to respond.

System selection is not set to
Heat.

Set system selection to Heat.

Heating setpoint is below room
temperature.

Check heating setpoint. Set heating setpoint to desired
temperature.

Cooling will not come
on.

No power to the thermostat.

Check for 24 Vac between R and Y terminals.

If missing 24 Vac:
Check if the circuit breaker is tripped—reset the circuit breaker.
Check if the system fuse is blown—replace the fuse.
Check if the power switch on the HVAC equipment is in the  
Off position—set to the On position.
Check wiring between thermostat and HVAC equipment—replace
any broken wires and tighten any loose connections.
If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off time is
activated.

Wait up to five minutes for the system to respond. Enter Installer
Setup number 39. Reconfigure minimum off time (if required).

System selection is not set to
Cool.

Set system selection to Cool.

Cool setpoint is above room
temperature.

Check cooling setpoint. Set cooling setpoint to desired
temperature.

Heating or cooling
come on momen -
tarily and shut off

Heat or cool circuit is opening
up or becoming high
impedance.

Add resistor in parallel with load or install interface relay.

System on indicator
(flame=heat,
snowflake=cool)   

Fan operation set for 0 (con-
ventional heat) when it should
be set for 1 (electric heat).

Enter Installer Setup number 2 and reconfigure the fan operation.

 displays, but no
warm or cool air is
coming from the
registers.

Conventional heating  
equipment turns on the fan
when the furnace has  
warmed up to a setpoint.

Wait a minute after seeing the on indicator and then check the
registers.

Heating or cooling equipment
is not operating.

Verify operation of heating or cooling equipment in self-test.

Outdoor temperature
not displayed

Option  not  activated.

Enter Installer Setup number 24 and set to 1. Thermostat must have

OT terminals and a TAYSENS100A installed.

or is incorrect.

Outdoor sensor is connected
incorrectly.

Refer to TAYSENS100A installation instructions and check wiring
between the thermostat and sensor.

Wrong sensor.

Replace sensor with TAYSENS100A sensor.

Filter expired.

Refer to the 

Filter Indication  section in the Owner’s Guide, Pub.  

No. 22-5127-04.

System on indicator
reads Filter and
backlight is flashing.

Filter expired.

Refer to the 

Filter Indication  section.

Time displaying digits
as three E’s (EEE).

Internal memory failure.

Contact distributor or retailer.

Содержание XT300C

Страница 1: ...heck the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing...

Страница 2: ...inal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat WIRES THROUGH WALL WALL MOUNTING HOLES M15044 MOUNTING SCR...

Страница 3: ...E BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP AND SYSTEM TEST DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM...

Страница 4: ...crease To scroll the Installer Setup numbers backwards press Time To exit the Installer Setup press Run Program CAUTION Equipment Damage Hazard Can cause permanent equipment damage Electric heat syste...

Страница 5: ...eat mode Heating cycle rate 4 5 5 5 cph recommended 3 6 or 9 cph not recommended 3 6 or 9 3 3 cph 6 6 cph 9 9 cph Cooling cycle rate 9 3 3 3 cph recommended 2 or 5 cph not recommended 2 or 5 2 2 cph 5...

Страница 6: ...5 the compressor will be on during call for heat Minimum On Time Cool 33 10 10 minute minimum on time for compressor 0 thru 15 Minimum number of minutes 0 thru 15 the compressor will be on during call...

Страница 7: ...ogram System Filter Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy M12954 Daylight Time AM DST Tue Set Day Time M12955 Run Program Aut...

Страница 8: ...Refer to Table 5 for the directions and results of the specific tests Fig 13 Display of all the segments of the LCD NOTE Press Time to advance to the next test and Time to go back to the previous tes...

Страница 9: ...splays Copy 60 12 Copy test number displays System select models 60 3 System test number displays Fan select models 60 10 Fan test number displays Set Current Day Time 60 1 Set Current Day Time test n...

Страница 10: ...ot come on Thermostat is not being powered Check for 24 Vac between R and W terminals Check if the circuit breaker is tripped reset the circuit breaker Check if the system fuse is blown replace the fu...

Страница 11: ...utes for the system to respond Enter Installer Setup number 39 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool Cool setpoint is above room tem...

Страница 12: ...AMMABLE HEAT COOL THERMOSTAT 69 1212 1 Pub No 18 HD25D1 3 69 1212 1 T C Rev 3 99 American Standard Inc Troup Highway Tyler TX 75711 9010 Printed in U S A on recycled paper containing at least 10 post...

Отзывы: