XT300C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

5

69-1212—1

Pub. No. 18-HD25D1-3

IMPORTANT

Only configurable numbers display. Example: Installer Setup Number 1 does not display because it is not configurable.
Review the factory settings in Table 3 and make any desired changes in the Actual Settings column. When the Installer
Setup is complete, review the settings to confirm that they match the system and the boxes you checked in the
Customizing Your Thermostat chart located in the Owners Guide.

Table  3. Installer Setup Options for the XT300C.

(continued)

Press Time   

▲ 

or

 ▼ 

 

Press Increase 

 or Decrease 

 to change setting

Installer   

Factory Setting

Other Choices

Actual

Select

Setup Number

Display

Description

Display

Description

Setting

Programming

42
Press Time 

▼ 

to

bypass 3–41 and
go directly to
setup #42

0

7-day programming

1 or 2

1—24-hour programming
2—No programming

Fan operation

2

0

Conventional applica-

tions where
equipment controls
fan operation in heat
mode

1

Heat pump or electric heat
applications where
thermostat controls fan
operation in heat mode

Heating cycle
rate

4

5

5—5 cph
recommended
3, 6 or 9 cph not
recommended

3, 6 or 9

3—3 cph
6—6 cph
9—9 cph

Cooling cycle
rate

9

3

3—3 cph
recommended   
2 or 5 cph not
recommended

2 or 5

2—2 cph
5—5 cph

System setting
adjustment   

12

0

Auto  changeover

1 or 2

1—Manual changeover

2—Auto changeover only

Adaptive
Intelligent
Recovery™
control

13  

0

Adaptive  Intelligent
Recovery (a
Honeywell trademark)
control is activated
(system starts early so
setpoint is reached by
start of program
period)

1

Conventional recovery
(system starts recovery at
programmed time)

Degree
temperature
display

14

0

Temperature displays
in 

°

F

1

Temperature displays in 

°

C

Clock format   

16

0

12-hour clock format

1

24-hour clock format

Extended fan
operation in
heating

a

19  

0

No extended fan
operation after the call
for heat ends

1, 2 or 3

1—Fan operation extends
30 seconds after the call
ends.
2—Fan operation extends
60 seconds after the call
ends.
3 —Fan operation extends
90 seconds after the call
ends.

Extended fan
operation in
cooling   

20  

0

No extended fan
operation after the call
for cool ends

1, 2 or 3

1—Fan operation extends
30 seconds after the call
ends.
2—Fan operation extends
60 seconds after the call
ends.
3 —Fan operation extends
90 seconds after the call
ends.

Содержание XT300C

Страница 1: ...heck the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing...

Страница 2: ...inal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat WIRES THROUGH WALL WALL MOUNTING HOLES M15044 MOUNTING SCR...

Страница 3: ...E BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP AND SYSTEM TEST DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM...

Страница 4: ...crease To scroll the Installer Setup numbers backwards press Time To exit the Installer Setup press Run Program CAUTION Equipment Damage Hazard Can cause permanent equipment damage Electric heat syste...

Страница 5: ...eat mode Heating cycle rate 4 5 5 5 cph recommended 3 6 or 9 cph not recommended 3 6 or 9 3 3 cph 6 6 cph 9 9 cph Cooling cycle rate 9 3 3 3 cph recommended 2 or 5 cph not recommended 2 or 5 2 2 cph 5...

Страница 6: ...5 the compressor will be on during call for heat Minimum On Time Cool 33 10 10 minute minimum on time for compressor 0 thru 15 Minimum number of minutes 0 thru 15 the compressor will be on during call...

Страница 7: ...ogram System Filter Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy M12954 Daylight Time AM DST Tue Set Day Time M12955 Run Program Aut...

Страница 8: ...Refer to Table 5 for the directions and results of the specific tests Fig 13 Display of all the segments of the LCD NOTE Press Time to advance to the next test and Time to go back to the previous tes...

Страница 9: ...splays Copy 60 12 Copy test number displays System select models 60 3 System test number displays Fan select models 60 10 Fan test number displays Set Current Day Time 60 1 Set Current Day Time test n...

Страница 10: ...ot come on Thermostat is not being powered Check for 24 Vac between R and W terminals Check if the circuit breaker is tripped reset the circuit breaker Check if the system fuse is blown replace the fu...

Страница 11: ...utes for the system to respond Enter Installer Setup number 39 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool Cool setpoint is above room tem...

Страница 12: ...AMMABLE HEAT COOL THERMOSTAT 69 1212 1 Pub No 18 HD25D1 3 69 1212 1 T C Rev 3 99 American Standard Inc Troup Highway Tyler TX 75711 9010 Printed in U S A on recycled paper containing at least 10 post...

Отзывы: