XT300C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

69-1212—1

Pub. No. 18-HD25D1-3

INSTALLER SELF-TEST

Use the Installer Self-Test to check the thermostat operation.
Refer to Table 4 for a list of the available self-tests.

CAUTION

Equipment Damage Hazard.
Equipment damage can occur if the compressor
is cycled too quickly.
The minimum off time is deactivated during the
Installer Self-Test.
Perform the test so that the compressor is cycled
slowly.

To start the self-test:
Press and hold the Increase 

 and Decrease 

 keys at the

same time until all display segments and the number 10
appears (all displays segments appear for approximately
three seconds before the test number displays). See
Figs. 13 and 14.

Table  4. Tests Available In The Installer Self-Test.

Aux Ht

Heat

Auto

System

Fan

Off

Auto

Wake

Mon

Wait

In

Room

Outdoor

Auto 

Sav

AM

PM

Hold for

Cool

Repl Batt

On

Recovery

DST

Cool

TueWedThuFriSatSun

LeaveReturnSleep

M17111

Set Program

Set Day/Time

Start Time

Temporary Setting Enrg

Em Heat

Em Ht

M10257A

TEST NUMBER

Fig. 14. Display of test number.

Refer to Table 5 for the directions and results of the specific tests.

Fig. 13. Display of all the segments of the LCD.

NOTE:

Press Time 

 to advance to the next test and Time 

 to go back to the previous test. Press Run Program to exit the

self-test. This mode times out 5 minutes after the last key press.

Table 5. Installer Self-Test Options.

(

continued)

Test   
Number Self-Test Description

10

Heating Equipment

30

Cooling Equipment

40

Fan Equipment

50

Comfort-R Terminals (H-H)

60

Keyboard Operation

70

Device Information

Key to
Press

Test
Number

Description

Heating Equipment Self-Test (10)

Time 

10

Enter heating equipment self-test.   

Temp 

11

First stage heat turns on. When Installer Setup number 2 is 1, the system fan is also energized.

Temp 

10

First stage heat turns off.

Cooling Equipment Self-Test (30)

Time 

30

Enter cooling equipment self-test.  

Temp

  ▲

31

First stage cool and fan turn on.

Temp 

30

First stage cool and fan turn off.

Fan Equipment Self-Test (40)

Time 

40

Enter fan equipment self-test.

Temp 

41

Fan turns on.

Temp 

40

Fan turns off.

Comfort-R Terminals Self-Test (50)

Temp 

50

Enter Comfort-R self-test.

Temp 

51

Reads HH terminals. If the terminals are open and Comfort-R is enabled, display reads  
% humidity. If the terminals are closed no % humidity displays.

Содержание XT300C

Страница 1: ...heck the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing...

Страница 2: ...inal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat WIRES THROUGH WALL WALL MOUNTING HOLES M15044 MOUNTING SCR...

Страница 3: ...E BETWEEN DAYLIGHT SAVINGS AND STANDARD TIME INCREASE TIME SETTING OR SCROLL FORWARD THROUGH INSTALLER SETUP AND SYSTEM TEST DECREASE TIME SETTING OR SCROLL BACKWARD THROUGH INSTALLER SETUP AND SYSTEM...

Страница 4: ...crease To scroll the Installer Setup numbers backwards press Time To exit the Installer Setup press Run Program CAUTION Equipment Damage Hazard Can cause permanent equipment damage Electric heat syste...

Страница 5: ...eat mode Heating cycle rate 4 5 5 5 cph recommended 3 6 or 9 cph not recommended 3 6 or 9 3 3 cph 6 6 cph 9 9 cph Cooling cycle rate 9 3 3 3 cph recommended 2 or 5 cph not recommended 2 or 5 2 2 cph 5...

Страница 6: ...5 the compressor will be on during call for heat Minimum On Time Cool 33 10 10 minute minimum on time for compressor 0 thru 15 Minimum number of minutes 0 thru 15 the compressor will be on during call...

Страница 7: ...ogram System Filter Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy M12954 Daylight Time AM DST Tue Set Day Time M12955 Run Program Aut...

Страница 8: ...Refer to Table 5 for the directions and results of the specific tests Fig 13 Display of all the segments of the LCD NOTE Press Time to advance to the next test and Time to go back to the previous tes...

Страница 9: ...splays Copy 60 12 Copy test number displays System select models 60 3 System test number displays Fan select models 60 10 Fan test number displays Set Current Day Time 60 1 Set Current Day Time test n...

Страница 10: ...ot come on Thermostat is not being powered Check for 24 Vac between R and W terminals Check if the circuit breaker is tripped reset the circuit breaker Check if the system fuse is blown replace the fu...

Страница 11: ...utes for the system to respond Enter Installer Setup number 39 Reconfigure minimum off time if required System selection is not set to Cool Set system selection to Cool Cool setpoint is above room tem...