64
VAV-SVX01C-EN
Troubleshooting
Wireless Zone Sensor Failure Procedures
In the event that the UCM reports an incorrect zone Temperature/sepoint, properly inspect the
following:
Note:
No special tools or software are necessary to service and test the wireless zone sensor
system. The system can be testing by using the following: 1) LEDs 1, 2, 3, and 5 on the sensor
and on the receiver; 2) The Test button (S5) on the sensor; 3) The address test mode on the
receiver; and 4) A common volt-ohm meter.
Diagnostics
Note:
Reading diagnostics can show if the sensor has an issue or it has not been setup properly.
Use this information as a starting point
•
LED1, LED2, and LED3 will respond to diagnostics by exhibiting specific blinking patterns. They
will occur on the sensor as a result of pressing the Test button (S5) (
Table 18, p. 65
). They will
occur on the receiver independently of any user action (
Table 18, p. 65
).
Figure 36. Wireless sensor set components with base plates removed
Table 15. Diagnostics: LED1, LED2, LED3 on the sensor
User Action
LED Display
(a)
(a) Blink pattern is On for ¼ s, Off for ¼ s, with 2 s Off between repetitions.
Indicates…
Press Test
Button (SS)
LED1:Off
LED2:Off
LED3: 1-blink pattern repeated 3 times
Disassociated:
* Sensor is not associated with a receiver
Press Test
Button (SS)
LED1:Off
LED2:Off
LED3: 2-blink pattern repeated 3 times
Address set to 000:
* Address not set to between 001-999
Press Test
Button (SS)
LED1:Off
LED2:Off
LED3: 3-blink pattern repeated 3 times
Not Configured:
* Sensor configuration properties not properly set
(defective sensor)
Press Test
Button (SS)
LED1:Off
LED2:Off
LED3: 4-blink pattern repeated 3 times
Input Voltage Too High:
* No RF transmission is permitted with an input
battery voltage greater than 3/9 V
LED 1
LED 2
LED 3
LED 5
LED 1
LED 2
LED 3
LED 5
Содержание VAV-UCM 4.2
Страница 1: ...May 2010 VAV SVX01C EN Installation Operation Maintenance VAV UCM 4 2...
Страница 81: ...VAV SVX01C EN 81 Troubleshooting Figure 46 Single duct with single phase voltage electric heat...
Страница 82: ...82 VAV SVX01C EN Troubleshooting Figure 47 Single duct with three phase voltage electric heat...
Страница 83: ...VAV SVX01C EN 83 Troubleshooting Figure 48 SCR PSC fan powered with single phase voltage electric heat...
Страница 84: ...84 VAV SVX01C EN Troubleshooting Figure 49 SCR PSC fan powered with three phase voltage electric heat...
Страница 85: ...VAV SVX01C EN 85 Troubleshooting Figure 50 ECM fan powered with single phase voltage electric heat...
Страница 86: ...86 VAV SVX01C EN Troubleshooting Figure 51 ECM fan powered with three phase voltage electric heat...