14
VAV-SVX01C-EN
UCM 4.2 Installation and Wiring
•
If local codes require enclosed conductors, the zone sensor wires should be installed in conduit.
Do not route zone sensor wires in conduit with 24 VAC or other high power conducting wires.
Multiple UCM’s Per Zone Sensor
Up to three (3) UCM’s may be connected to a single zone sensor and thumbwheel set point.
•
Connect terminal connections TB3-1, TB3-2, and TB3-3 in parallel (i.e. daisy chain) from the
master UCM to the slaved UCM(s).
Note:
Proper polarity must be maintained.
•
Cut jumper wires W1 and W2 on the slaved UCM’s (never cut jumper wires W1 and W2 on the
master UCM).
Multiple UCM’s per Auxiliary Duct Temperature Sensor
Up to three (3) UCMs may be connected to a single auxiliary duct temperature sensor.
•
Connect terminal connections TB3-5 and TB3-6 in parallel (i.e. daisy chain) from the master
UCM to the slaved UCM(s).
Note:
Proper polarity must be maintained.
•
Cut jumper wire W4 on the slaved UCMs (never cut jumper wire W4 on the master UCM).
Zone Sensor Hardwired Option
Depending on the zone sensor options used, a maximum of five wires may be required to run from
the UCM to the zone sensor. The zone sensor options are:
•
Zone sensor only (2 wires) - Part Number X13511528010
•
Sensor with night set back - Part Number X13511530010
•
Zone sensor with external adjustable - Part Number X13511529010
•
Zone sensor with external adjustable night set back, timed override (TOV) on/cancel button -
Part Number X13511527010
•
Digital zone sensor - Part Number X13511530010
•
Communications jack - Part Number X13651467020 (for one box of 12)
Note:
All wiring from the zone sensor to the Communication link must be twisted shielded pair
wiring.
Zone Sensor Wireless Option
Wireless Zone Sensor
Receiver is used to receive a signal from the wireless zone sensor and can be factory installed- Part
Number X13790855010.
The wiring harness connects the receiver to the UCM 4.2 - Part Number X19051672010.
Zone Sensor
The wireless zone sensor with night setback timed override (TOV) on/cancel button. Also can be
ordered for Celsius and Fahrenheit setpoint adjustment - Part Number X13790492010 (F),
X13790494010 (C). Digital Wireless Part Number: X13790822010.
Содержание VAV-UCM 4.2
Страница 1: ...May 2010 VAV SVX01C EN Installation Operation Maintenance VAV UCM 4 2...
Страница 81: ...VAV SVX01C EN 81 Troubleshooting Figure 46 Single duct with single phase voltage electric heat...
Страница 82: ...82 VAV SVX01C EN Troubleshooting Figure 47 Single duct with three phase voltage electric heat...
Страница 83: ...VAV SVX01C EN 83 Troubleshooting Figure 48 SCR PSC fan powered with single phase voltage electric heat...
Страница 84: ...84 VAV SVX01C EN Troubleshooting Figure 49 SCR PSC fan powered with three phase voltage electric heat...
Страница 85: ...VAV SVX01C EN 85 Troubleshooting Figure 50 ECM fan powered with single phase voltage electric heat...
Страница 86: ...86 VAV SVX01C EN Troubleshooting Figure 51 ECM fan powered with three phase voltage electric heat...