background image

15

USER GUIDE

524 Control Installation and User Guide

Troubleshooting

Symptom

Possible Cause

Action

Display will not come on

Loss of 24VAC between R & C at the Control

1) Check wiring between R & C 

2) Check transformer for 24VAC output 

3) Check for broken or shorted thermostat wire

Indoor Temperature 

display is incorrect

1) Indoor temperature display needs calibrating 

(always allow 1 hour before calibrating after 

any power cycle) 

2) Heat from the touchscreen is being trapped 

within the body of the control

1) Calibrate indoor temperature sensor  

 

 

2) Relocate the control away from any competing air sources 

or redirect the air sources away from the control

Room temperature 

overshoots the desired 

setpoint in cooling mode

1) The delta “Off” in cooling mode is set to a 

negative number 

2) Minimum compressor on time has not been 

met

1) Intended operation; if objectionable, change the delta “Off” 

to 0 degrees 

2) Intended operation; if objectionable, lower minimum on time 

(lowest setting available is 3 minutes)

Room temperature 

overshoots the desired 

setpoint in heating mode

Minimum compressor/indoor heat on time has 

not been met

Intended operation; if objectionable, lower the minimum on 

time (lowest setting available is 3 minutes)

Cooling will not come on

1) System mode is not set to Cool/Auto or 

setpoint is set too high 

2) Delta “On” for cooling is set too high 

3) Minimum off time delay is being enforced 

 

4) Cooling system may need service

1) Select the correct system mode and/or lower the setpoint 

 

2) Change the delta “On” setting for cooling mode 

3) Intended operation; if objectionable, lower the minimum off 

time delay (lowest setting is 5 minutes) 

4) Check/repair system

Heating will not come on

1) System mode is not set to Heat/Auto or 

setpoint is set too low 

2) Delta “On” for heating is set too high 

3) Minimum off time delay is being enforced 

4) Heating system may need service

1) Select the correct system mode and/or raise the setpoint 

 

2) Change the delta “On” setting for heating mode 

3) Intended operation; if objectionable, lower the minimum off 

time delay (lowest setting is 5 minutes) 

4) Check/repair system

Heating or Cooling is 

being displayed, but no 

air coming from registers/

vents

1) Fan delay time has not expired

 

2) System is not operating properly

1) Wait one minute for blower delay to end, then recheck 

register/grills

2) Check/repair system

Fan runs all the time

1) Fan mode is set to “On” or “Circ” 

2) System is not operating properly

1) Intended operation; if objectionable, change fan mode to “Auto” 

2) Check/repair system

Fan is set to “On” but not 

running

1) System is not operating properly

1) Check/repair system

On Nexia Climate tab, 

524 icon remains gray 

and cannot be selected.

1) Bridge and 524 are not able to communicate 

via Z-wave.

1) Verify Nexia bridge is not located inside of an enclosure 

and is not sitting directly on other electrical equipment. 

2) If bridge and 524 are more than 30’ apart, enroll a Z-wave 

repeater (plug-in dimmer or appliance module) into the bridge, 

and plug repeater into outlet midway between bridge and 524. 

3) Temporarily turn off other nearby wireless transmitters such 

as baby monitors 

After checking 1-3, click on Climate page and allow 1-2 

minutes for icon to turn blue

System cools when it 

should be heating or 

heats when it should be 

cooling

1) Energize Reversing Valve setting is reversed 1) Navigate to Installer Settings:Equipment Type:Energize 

Reversing Valve. If setting is set to With Cool, change to With 

Heat. If setting is set to With Heat, change to With Cool.

Troubleshooting

Содержание TZEMT524AA21MA

Страница 1: ...is not compatible with the following system types Radiant floor systems Wall heating systems Î Î NOTE A 24 Volt common and hot wire MUST be connected to the control for operation CAUTION ELECTRICAL HAZARD Can cause electrical shock or equipment damage Disconnect power to heating and cooling equip ment before beginning installation MERCURY NOTICE When this Comfort Control is replacing an old thermo...

Страница 2: ... 2 If your existing thermostat has a terminal named C COM X or B with a wire connected to it skip to 6 Label and remove old thermostat wires on page 3 The B terminal on Trane American Standard Weathertron and York thermostats is the 24V Common terminal On all other thermostats it servers another purpose 5 Connecting a 24V common wire 1 Locate all unused disconnected wires from the thermostat wire ...

Страница 3: ... you had to connect a new 24 VAC common wire you will use the C label on that wire If you have a W terminal use the W1 label on that wire If your thermostat has any terminals with names that do not match any on the label write down the terminal names and wire colors for later reference TAKE A PICTURE It is recommended that you take a picture that clearly shows the wires attached to your existing t...

Страница 4: ...equipment consult a qualified HVAC professional before proceeding Gas Hydronic With Fan Hydronic Without Fan Electric You have a BOILER You have a BOILER and an air handler You have a BOILER and a radiator or baseboard heaters You have an ELECTRIC furnace or an air handler INDOOR UNIT TYPE Your Indoor Heat Stages INDOOR HEAT STAGES Observe the wires connected to your existing thermostat and follow...

Страница 5: ...ll the wires through the hole in center of wall plate 2 Position the new wall plate over the existing opening 3 Attach wall plate to wall using the two screws provided Do not overtighten 12 Review the wiring chart information Refer the chart below to determine which wires connect to the corresponding terminal on the 524 Control Note than you may have more than one wire connected to a single termin...

Страница 6: ... Installer Settings is displayed 3 Press Select Equipment Type is Displayed 4 Press Select Outdoor Unit Type with the current selection is displayed 5 Press Select Using the up and down arrows navigate to the type of outdoor unit you have as you determined in 8 Identify your system type on page 4 6 Press Done Press Next Indoor Unit Type with the current selection is displayed 7 Press Select Using ...

Страница 7: ... familiar with HVAC systems Menu Item Equipment Settings Setting Range Description Compressor Stage 1 MRT 3 9 Minutes Select the minimum runtime MRT of stage 1 compressor operation Compressor MOT 5 9 minutes Select the minimum offtime MOT for compressor operation Indoor Heat Stage 1 MRT 3 9 Minutes Select the minimum runtime MRT of stage 1 indoor heat Indoor Heat Stage 2 MRT 3 9 Minutes Select the...

Страница 8: ...ription Blower On Delay Cooling 0 30 seconds Non Variable Speed blower only Select the cooling blower on delay Blower Off Delay Cooling 0 90 Seconds Non Variable Speed blower only Select the cooling blower off delay Blower On Delay Heating 0 30 Seconds Non Variable Speed blower only Select the compressor heating blower on delay Blower On Delay Heating 0 60 Seconds Select the hydronic heating blowe...

Страница 9: ...ule or by pressing the Setpoint Up Down buttons Pressing the setpoint button changes the setpoint screen The current mode is displayed at the top of the screen Adjust the setpoint by pressing the up or down arrows To change setpoint mode press the MODE button The heating and cooling setpoints will push each other if they are adjusted to within the minimum heat cool separation setting The default i...

Страница 10: ...creen times out Backlight Timeout 0 90 Seconds 20 Select how long after the last button press before the backlight dims Backlight On Percent 0 100 Percent Select the screen brightness when the backlight is lit Backlight Off Percent 0 100 Percent Select the screen brightness when the backlight dims Buzzer Enable Yes No Select whether button presses are audible Security Unlocked Display Lock Guest A...

Страница 11: ...n all selections have been made press the Done button to register your changes and exit this menu item Press Next or Back to navigate to the next or previous menu item Menu Item Reminders Setting Range Description Filtration Enable Yes No Selecting yes enables the Filter Reminder feature System Maint Enable Yes No Selecting yes enables the System Maintenance Reminder feature When all selections ha...

Страница 12: ...s NEXT or BACK until the desired day is displayed This is the from day and will be a day for which you previously programmed a schedule 4 Press SELECT 5 Press YES to copy the schedule to this day or NO to skip this day Cycle through the days of the week until your selection is complete 6 Press DONE to complete the copying process Press DONE again to return to the User Settings menu Schedule Menu I...

Страница 13: ...while enrollment is taking place Enrollment is complete when the orange light becomes solid 3 Verify enrollment of the 524 Control 1 Press MENU from the 524 Control Home screen 2 Press NEXT to advance to the About screen and press SELECT 3 Press NEXT to advance through the menu options to Node ID If the number listed there is anything other than 00 the 524 Control has been successfully enrolled If...

Страница 14: ...Wave Thermostat General V2 Device class used by the Z Wave control If you are using a controller that is not a Nexia bridge consult the instructions that came with the controller to find out how to enroll and exclude devices Installer settings are described earlier in this document Menu Item Exclude from Net About Installer Settings Clean Screen About Setting Description Version Current firmware v...

Страница 15: ... system Heating will not come on 1 System mode is not set to Heat Auto or setpoint is set too low 2 Delta On for heating is set too high 3 Minimum off time delay is being enforced 4 Heating system may need service 1 Select the correct system mode and or raise the setpoint 2 Change the delta On setting for heating mode 3 Intended operation if objectionable lower the minimum off time delay lowest se...

Страница 16: ... to the home If yes temporarily unpower the new equipment and then re test 524 Features TZEMT524AA21MA Comfort Control Features 24v Z Wave comfort control Remote access via smart phone tablet or P C requires a Nexia bridge Internet access and a Nexia Home Intelligence account Interactive 4 3 touchscreen 7 Day programmable 4 periods day Filter and maintenance service reminders Energy Savings Mode E...

Страница 17: ...aints solvents or other chemicals Further the terms and conditions of this One 1 Year Limited Electronics and Mechanical Warranty do not apply to Purchased Product when 1 used in common area applications 2 used for purposes for which it was not designed or intended 3 subjected to alteration modification abuse misuse negligence or accident improper storage improper installation or maintenance or op...

Страница 18: ...ly approved by the party responsible for compliance could void the user s authority to operate the equipment Les changements ou modifications non approuvés expressément par la partie responsable de la conformité pourrait annuler l autorité de l utilisateur à faire fonctionner l équipement This device complies with Industry Canada licence exempt RSS standard s Operation is subject to the following ...

Страница 19: ...19 USER GUIDE 524 Control Installation and User Guide ...

Страница 20: ...ww trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Literature Order Number 18 HD46D1 1 File number Supersedes NA Date 12 04 2014 Trane ...

Отзывы: