background image

3

INSTALLATION GUIDE

524 Control Installation and User Guide

5.  Find a wire from the thermostat bundle that is unused at the thermostat and at the furnace.

It is possible that one of the unused wires at the thermostat will already be connected to the 24 VAC common terminal at the 
furnace. If so, go to “6 Label and remove old thermostat wires” on page 3.

6.  Connect the unused wire to the 24 VAC terminal, then replace the furnace cover. 

The 24 VAC common wire is typically (but not always) blue in color. If the blue 
wire has been unused, it is recommended that you use the blue wire.

 If you are unsure about connecting this wire or you do not have any 

unused wires at the thermostat, contact Customer Service at 877-288-7707.

Label and remove old thermostat wires

1.  Label the wires on your existing thermostat to match terminal names.

DO NOT USE WIRE COLORS TO CHOSE LABELS. THE TERMINAL NAME IS 
WHAT IS IMPORTANT.

2.  Locate the wiring labels included with the new thermostat. 
3.  Observe where each wire is connected to the existing thermostat and find the 

letter shown next to that wire terminal.

4.  Attach the corresponding label the wire.

IMPORTANT NOTES:
If you have a short jumper wire between two terminals, remove the jumper and 
do not label it. This jumper wire is not required on the new thermostat.
If you had to connect a new 24 VAC common wire, you will use the “C” label on 
that wire.
If you have a W terminal, use the W1 label on that wire.
If your thermostat has any terminals with names that do not match any on the label,  write down the terminal names and wire 
colors for later reference.

 TAKE A PICTURE

It is recommended that you take a picture that clearly shows the wires attached to your existing thermostat terminals. This could be 
needed later if you have troubles with your installation.

Remove existing wall plate.

The 524 Control is designed for installation in climate controlled living spaces. It is recommended to place the unit in a central 

location with good circulation. Avoid exterior walls and areas near windows, doors, vents or concealed pipes or chimneys.

NOTE: DURING THIS PROCESS, MAKE SURE THAT THE WIRES DO NOT PULL BACK INTO WALL OPENING.

5.  Detach all wires from wall plate.
6.  Remove all screws attaching the wall plate to the wall and remove wall plate.
7.  See “MERCURY NOTICE”.

 MERCURY NOTICE

When this control is replacing a control that contains mercury in a sealed tube, dispose of the old control properly. Contact 
your local waste management authority for instructions regarding recycling and proper disposal. A listing of heating, ventilating 
and air conditioning wholesalers that participate in the Thermostat Recycling Corporation’s recycling program are available at 
www.thermostat-recyle.org .

G

W

R

C

Connect

 wire

Y

Y

G

W1

C

R

G

Rc R

C

Wire colors and 
letters may vary

!

W1

Содержание TZEMT524AA21MA

Страница 1: ...is not compatible with the following system types Radiant floor systems Wall heating systems Î Î NOTE A 24 Volt common and hot wire MUST be connected to the control for operation CAUTION ELECTRICAL HAZARD Can cause electrical shock or equipment damage Disconnect power to heating and cooling equip ment before beginning installation MERCURY NOTICE When this Comfort Control is replacing an old thermo...

Страница 2: ... 2 If your existing thermostat has a terminal named C COM X or B with a wire connected to it skip to 6 Label and remove old thermostat wires on page 3 The B terminal on Trane American Standard Weathertron and York thermostats is the 24V Common terminal On all other thermostats it servers another purpose 5 Connecting a 24V common wire 1 Locate all unused disconnected wires from the thermostat wire ...

Страница 3: ... you had to connect a new 24 VAC common wire you will use the C label on that wire If you have a W terminal use the W1 label on that wire If your thermostat has any terminals with names that do not match any on the label write down the terminal names and wire colors for later reference TAKE A PICTURE It is recommended that you take a picture that clearly shows the wires attached to your existing t...

Страница 4: ...equipment consult a qualified HVAC professional before proceeding Gas Hydronic With Fan Hydronic Without Fan Electric You have a BOILER You have a BOILER and an air handler You have a BOILER and a radiator or baseboard heaters You have an ELECTRIC furnace or an air handler INDOOR UNIT TYPE Your Indoor Heat Stages INDOOR HEAT STAGES Observe the wires connected to your existing thermostat and follow...

Страница 5: ...ll the wires through the hole in center of wall plate 2 Position the new wall plate over the existing opening 3 Attach wall plate to wall using the two screws provided Do not overtighten 12 Review the wiring chart information Refer the chart below to determine which wires connect to the corresponding terminal on the 524 Control Note than you may have more than one wire connected to a single termin...

Страница 6: ... Installer Settings is displayed 3 Press Select Equipment Type is Displayed 4 Press Select Outdoor Unit Type with the current selection is displayed 5 Press Select Using the up and down arrows navigate to the type of outdoor unit you have as you determined in 8 Identify your system type on page 4 6 Press Done Press Next Indoor Unit Type with the current selection is displayed 7 Press Select Using ...

Страница 7: ... familiar with HVAC systems Menu Item Equipment Settings Setting Range Description Compressor Stage 1 MRT 3 9 Minutes Select the minimum runtime MRT of stage 1 compressor operation Compressor MOT 5 9 minutes Select the minimum offtime MOT for compressor operation Indoor Heat Stage 1 MRT 3 9 Minutes Select the minimum runtime MRT of stage 1 indoor heat Indoor Heat Stage 2 MRT 3 9 Minutes Select the...

Страница 8: ...ription Blower On Delay Cooling 0 30 seconds Non Variable Speed blower only Select the cooling blower on delay Blower Off Delay Cooling 0 90 Seconds Non Variable Speed blower only Select the cooling blower off delay Blower On Delay Heating 0 30 Seconds Non Variable Speed blower only Select the compressor heating blower on delay Blower On Delay Heating 0 60 Seconds Select the hydronic heating blowe...

Страница 9: ...ule or by pressing the Setpoint Up Down buttons Pressing the setpoint button changes the setpoint screen The current mode is displayed at the top of the screen Adjust the setpoint by pressing the up or down arrows To change setpoint mode press the MODE button The heating and cooling setpoints will push each other if they are adjusted to within the minimum heat cool separation setting The default i...

Страница 10: ...creen times out Backlight Timeout 0 90 Seconds 20 Select how long after the last button press before the backlight dims Backlight On Percent 0 100 Percent Select the screen brightness when the backlight is lit Backlight Off Percent 0 100 Percent Select the screen brightness when the backlight dims Buzzer Enable Yes No Select whether button presses are audible Security Unlocked Display Lock Guest A...

Страница 11: ...n all selections have been made press the Done button to register your changes and exit this menu item Press Next or Back to navigate to the next or previous menu item Menu Item Reminders Setting Range Description Filtration Enable Yes No Selecting yes enables the Filter Reminder feature System Maint Enable Yes No Selecting yes enables the System Maintenance Reminder feature When all selections ha...

Страница 12: ...s NEXT or BACK until the desired day is displayed This is the from day and will be a day for which you previously programmed a schedule 4 Press SELECT 5 Press YES to copy the schedule to this day or NO to skip this day Cycle through the days of the week until your selection is complete 6 Press DONE to complete the copying process Press DONE again to return to the User Settings menu Schedule Menu I...

Страница 13: ...while enrollment is taking place Enrollment is complete when the orange light becomes solid 3 Verify enrollment of the 524 Control 1 Press MENU from the 524 Control Home screen 2 Press NEXT to advance to the About screen and press SELECT 3 Press NEXT to advance through the menu options to Node ID If the number listed there is anything other than 00 the 524 Control has been successfully enrolled If...

Страница 14: ...Wave Thermostat General V2 Device class used by the Z Wave control If you are using a controller that is not a Nexia bridge consult the instructions that came with the controller to find out how to enroll and exclude devices Installer settings are described earlier in this document Menu Item Exclude from Net About Installer Settings Clean Screen About Setting Description Version Current firmware v...

Страница 15: ... system Heating will not come on 1 System mode is not set to Heat Auto or setpoint is set too low 2 Delta On for heating is set too high 3 Minimum off time delay is being enforced 4 Heating system may need service 1 Select the correct system mode and or raise the setpoint 2 Change the delta On setting for heating mode 3 Intended operation if objectionable lower the minimum off time delay lowest se...

Страница 16: ... to the home If yes temporarily unpower the new equipment and then re test 524 Features TZEMT524AA21MA Comfort Control Features 24v Z Wave comfort control Remote access via smart phone tablet or P C requires a Nexia bridge Internet access and a Nexia Home Intelligence account Interactive 4 3 touchscreen 7 Day programmable 4 periods day Filter and maintenance service reminders Energy Savings Mode E...

Страница 17: ...aints solvents or other chemicals Further the terms and conditions of this One 1 Year Limited Electronics and Mechanical Warranty do not apply to Purchased Product when 1 used in common area applications 2 used for purposes for which it was not designed or intended 3 subjected to alteration modification abuse misuse negligence or accident improper storage improper installation or maintenance or op...

Страница 18: ...ly approved by the party responsible for compliance could void the user s authority to operate the equipment Les changements ou modifications non approuvés expressément par la partie responsable de la conformité pourrait annuler l autorité de l utilisateur à faire fonctionner l équipement This device complies with Industry Canada licence exempt RSS standard s Operation is subject to the following ...

Страница 19: ...19 USER GUIDE 524 Control Installation and User Guide ...

Страница 20: ...ww trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Literature Order Number 18 HD46D1 1 File number Supersedes NA Date 12 04 2014 Trane ...

Отзывы: