RMWH-SVX001C-EN
7
Description
The TruSense™ RMWH Refrigerant Monitor provides
continuous monitoring of refrigerant gas levels for up to
16 points in nonhazardous areas. With the ability to read
down to 1 ppm, the device provides a response to a
refrigerant leak, supporting the safety of personnel and
the environment, and equipment efficiency. The device
uses patented Photoacoustic Infrared technology to allow
the accurate measurement of refrigerant gases with
minimum interference from other vapors. The device
monitors refrigerant gases up to 1000 ppm with an ability
to maintain a gas list through an internal refrigerant
library.
The TruSense™ RMWH Refrigerant Monitor minimizes
unnecessary maintenance costs associated with
calibration and sensors by utilizing a centralized sample
draw system. The device is factory calibrated for six
specific refrigerants, with the flexibility to adjust the gas of
interest in the field.
The device offers three levels of alarm—caution, warning,
and alarm—that are all configurable through the intuitive
touchscreen display. Fault and service notifications
provide alerts when servicing is necessary. Audible and
visual indications such as horns and strobes provide alerts
about refrigerant leaks.
Digital communications can be transmitted using the
Modbus remote terminal unit (RTU) or BACnet™ master/
slave token passing (MS/TP) protocol. Analog
communications can be transmitted using a 4–20 mA or
0–10 Vdc current loop.
The TruSense™ RMWH Refrigerant Monitor requires
minimal maintenance and incorporates predictive
diagnostics that continuously check key detector
components to ensure proper operation. When the device
is installed, operated, and maintained according to Trane’s
recommendations, it provides reliable protection and
long-term stability.
Identifying Your Unit
Figure 1.
Front of device
1. 7-in. resistive touchscreen user interface
2. Power indicator
Figure 2.
Back of device
1. Mounting locations (10 in. x 14-5/8 in.)
1
2
1
1
Содержание TruSense RMWH