Description
10
RMWH-SVX001C-EN
For a list of the registers that are available for exchange
with the MODBUS® controller, refer to
MODBUS Holding Registers,” p. 58
.
For a list of the BACnet® Objects that are available for
exchange with the BACnet® controller, refer to
.
Analog Communication
The device is capable of the following types of analog
outputs:
•
4–20 mA, isolated, current sourcing
•
0–10 Vdc for gas sample point identification
Full scale is 1000 ppm.
Normal gas readings are at 4–20 mA. The reading is
proportional to the detected gas concentration.
For the factory default of 100 percent full scale setting
(0.016 mA = 1 ppm), refer to the following table.
Table 1.
Scale analog output: 4–20 mA
Output (mA)
Gas Concentration (ppm)
4
0
5
63
6
125
7
188
8
250
9
313
10
375
11
438
12
500
13
563
14
625
15
688
16
750
17
813
18
875
19
937
20
1000
Table 2.
Analog output settings
Warm-up
• Default = 3.5 mA
• User adjustable between
0 and 3.75 mA
Calibration (non-configurable)
• 3.0 mA
Fault
• Default = 2.0 mA
• User adjustable between
0.5 and 3.75 mA
Device over range (non-configurable)
• 21 mA
The voltage output can be used to identify any active gas
sample line.
Table 3.
0–10 Vdc
Sample Line
Vdc
4 or 8 pt system
16 pt system
1
1
1.0
2
2
1.5
3
3
2.0
4
4
2.5
5
5
3.0
6
6
3.5
7
7
4.0
8
8
4.5
9
—
5.0
10
—
5.5
11
—
6.0
12
—
6.5
13
—
7.0
14
—
7.5
15
—
8.0
16
—
8.5
While the device is in calibration mode, the output is
10 Vdc.