Section
Register Name
Channel #
Index
Property
Notes
Gases Calibration
Next Cal Time
Gases
40090
Read
In days from 1970
Zero Cal Time
40091
Read
In days from 1970
Span Cal Time #00
40092
Read
In days from 1970 – R-11
Span Cal Time #01
40093
Read
In days from 1970 – R-12
Span Cal Time #02
40094
Read
In days from 1970 – R-22
Span Cal Time #03
40095
Read
In days from 1970 – R-123
Span Cal Time #04
40096
Read
In days from 1970 – R-134A
Span Cal Time #05
40097
Read
In days from 1970 – R-401A
Span Cal Time #06
40098
Read
In days from 1970 – R-404A
Span Cal Time #07
40099
Read
In days from 1970 – R-407A
Span Cal Time #08
40100
Read
In days from 1970 – R-407C
Span Cal Time #09
40101
Read
In days from 1970 – R-407F
Span Cal Time #10
40102
Read
In days from 1970 – R-410A
Span Cal Time #11
40103
Read
In days from 1970 – R-422A
Span Cal Time #12
40104
Read
In days from 1970 – R-422D
Span Cal Time #13
40105
Read
In days from 1970 – R-427A
Span Cal Time #14
40106
Read
In days from 1970 – R-507
Span Cal Time #15
40107
Read
In days from 1970 – R-513A
Span Cal Time #16
40108
Read
In days from 1970 – R-514A
Span Cal Time #17
40109
Read
In days from 1970 – R-1233zd(E)
Span Cal Time #18
40110
Read
In days from 1970 – R-1234yf
Span Cal Time #19
40111
Read
In days from 1970 – R-1234ze
Appendix D: MODBUS Holding Registers
60
RMWH-SVX001C-EN
RESET Button Actions
HiByte
LoByte
Description
0
channel#
Reset channel-specific alarms, channel#1-#16 = 0..15
0
255
Reset all channel-specific alarms
1
channel#
Reset channel-specific faults, channel#1-#16 = 0..15
1
255
Reset all channels-specific faults
2
255
Reset common faults
3
255
Reset all alarms and all faults
Unit Status Flags
Bit
Description
0x0001
Warm up
Set if warm-up time is pending
0x0002
Operating
Normal operating mode is set (after warm-up; not in calibration, fault, or alarm)
0x0004
Calibration
Set if calibration is in progress
0x0008
Fault
Set if failure is reported
0x0010
Alarm
Set if C/W/A level is achieved
0xFFE0
—
Reserved
Содержание TruSense RMWH
Страница 40: ...Routine Operation 40 RMWH SVX001C EN Use the scroll bar to see all of the available information ...
Страница 45: ...Diagnostics RMWH SVX001C EN 45 To see details about an error select it ...
Страница 66: ......
Страница 67: ......